![Eaton Greengate RC3 Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/eaton/greengate-rc3/greengate-rc3_installation-instructions-manual_4075203002.webp)
2
For more information see the Room Controller troubleshooting document
www.eaton.com/lightingsystems
Sample Placement Diagram
(For Example Purposes Only)
Wall/Corner Mount
Occupancy Sensor
Room Controller
(Above Entry Door)
Entry
Wallstation
Additional
Wallstation
Daylight
Sensor
W
indo
w
General On
Raise
Lower
Whiteboard
Quiet Time
AV Mode
General On
Off
The Room Controller is a room based system that
simplifies design, code compliance and installation. The
controller connects to occupancy sensors, daylighting
sensors, wallstations and receptacle control accessories
with provided Click & Go QuickConnect cables, providing
a completely operational, out-of-the-box solution. Control
up to three switched and three dimmed loads (dependent
on model ordered) without the need for post-installation
programming.
Additional advanced integration easily accomodates
Demand Response, Alert Mode, A/V Mode and Time Clock
requirements.
This document shows installation details regarding the
Room Controller and accessory products.
CAUTION
Bonding between conduit connections is not automatic and
must be provided as part of the installation.
Failure to install the Room Controller in the suggested
location (above the entry door) may lead to the provided
QuickConnect cabling being too short to reach the intended
accessory locations.
1
2
3
4
5
6
Integration Controls
Adjustable Skylights
Low En
dH
igh En
d
Energy Options
Statu
s
Reset
0-10V Gain Adjustmen
t
Dimmer 3
Dimmer 2
Dimmer 1
+
-
-
+
+
-
0-10V Dimming
0-10V Dimming Outputs
-
+
Dimmer 3
Dimmer 2
Dimmer 1
-
+
+
-
Blue - EM Line In Blue - EM Loads Out
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Black - Line In White/Black - 120V
N
White/Orange - 277V
N
Blue - Load In Ye
llow - Load 1 Ou
t
Red - Load 2 Out Purple - Load 3 Out
Energy Options DIP Switch
Demand Response Occupancy
Not Used
1 2
3
4
Default 10%
20%
30%
40%
Occ
Vac (default)
Time
Clock
Alert
Mode
Demand
Response
A/V
Mode
+
-
Integration Controls
+
-
+
-
+
-
Green
Black
Red
White
Adjustable Skylight
s
Sensors
Receptacle
BMS/Out
Switchpack
QuickConnect Cable
s
Sensors
Slider
Station
Wallstations
Room Controller Plastic Enclosure (Model RC3DE shown)
Room Controller Metal Enclosure (Model RC3DE-PL shown)
Specifications
Input/Output Voltage
120/277 VAC 50/60Hz
Maximim Combined Load
20A
Ballast:
20A (LED)
Incandescent:
15A
Motor Load:
1 HP @ 120 VAC
Emergency Output: (RC3DE only)
Ballast:
3A (LED)
Incandescent:
3A
Class 2 Dimming Output
0-10 VDC, sinks up to 100mA
per output for control of up to 50
compatible ballasts/drivers.
Operating Environment
32° F to 104° F (0° to 40° C)
For indoor use only.