Bringing the Room Controller Online

www.eaton.com/lightingsystems

Bringing the Room Controller Online

The Room Controller is pre-programmed and ready for operation out-of-the-box. If no adjustments are done, the unit will 

operate from occupancy sensors, daylighting and wallstations. 
To obtain maximum energy efficiency and occupant satisfaction, we recommend that you complete this short checklist to 

verify the unit is operating optimally for the space being controlled.

Room Controller Verification Checklist

Room Location: ____________________

1.

Initial Power Up Response

Apply power to the Room Controller.

Verify that all lighting loads turn on to full for 3 seconds before beginning normal operation.

2.

Verify Occupancy Sensor Operation

Verify that the occupancy sensor has been located properly to prevent false activation.

Wait 2 minutes from power-up, then place OAC or OAWC sensors in Test Mode by 

moving DIP Switch 10 out of its current position, wait 3 seconds, then put back into 

its original position.

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10 11 12

ON

Move around the controlled area, verifying that the ocupancy sensor LEDs flash with each motion and stop flashing when you stand still.

If not already ON, turn lighting ON from the wallstation controls. For any stations with Quiet Time buttons, make sure that Quiet Time 

Mode is de-activated (LED is not lit).

Leave the room and wait approximately one minute for the lighting to turn OFF.

If lighting does not turn OFF, refer to “Room Controller Troubleshooting” on page 23. Sensors will automatically exit Test Mode after a period of 5 

to 10 minutes (timing is dependent on sensor model) and begin automatically adjusting based on occupancy patterns.

3.

Verify Wallstation Operation

Check each wallstation for proper operation of intended loads.

4.

Set Minimum and Maximum Trim levels

Trim levels have been preset to approximately 90% maximum. Additional energy savings can be gained by adjusting the trim further if electric  

lighting contribution is over the target illuminance for the space.

Locate the position of the trim level adjustment dials on the Room Controller.

Low End

High En

d

Energ

y

Option

s

Statu

 eset

0-10V Gain Adjustmen

t

Dimmer 3

Dimmer 2

Dimmer 1

+

-

-

+

+

-

0-10V Dimming

Integration Controls

Adjustable Skylights

0-10V Dimming Outputs

-

+

Dimmer 3

Dimmer 2

Dimmer 1

-

+

+

-

Blue - EM Line In Blue - EM Loads Ou

t

CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.

Black - Line In White/Black - 120V 

N

White/Orange - 277V 

N

Blue - Load In Ye

llow - Load 1 Ou

t

Red - Load 2 Ou

t

Purple - Load 3 Out

Energy Options DIP Switch

Demand Response Occupancy

Not Used

1 2

3

4

Default 10%

20%

30%

40%

Occ

Vac (default)

Time

Clock

Alert

Mode

Demand

Response

A/V

Mode

+

-

Integration Controls

+

-

+

-

+

-

Green

Black

Red

White

Adjustable Skylight

s

Sensors

Receptacle

BMS/Out

Switchpack

QuickConnect Cable

s

Sensors

Slider

Station

Wallstations

Trim levels are being adjusted at night or shades have been used to darken the space during daylight hours.

Using the wallstations, turn ON all controlled lighting. For fluorescent lighting loads, wait one minute to allow lamps to warm up.

Using a small screwdriver, twist the maximum trim dial counter clockwise, then fully clockwise again. The lights will go full bright and the 

Room Controller will enter Adjustment Mode.

Turn the maximum trim adjustment dial counter-clockwise in small increments until the light level is at the desired maximum level.

Turn the minimum trim dial clockwise then fully counter clockwise. The light level in the room will go full dim.

Turn the minimum trim dial clockwise in small increments until you begin to notice the light level increasing in the monitored space, then 

turn the dial slightly counter clockwise from where this change begins.

Save the new trim settings and go back to normal operation by pressing the “All OFF” button on any wallstation.
If “All OFF” is not pressed, the controller will automatically save these settings after two minutes.

Содержание Greengate RC3

Страница 1: ...s from more than one power source Designed for indoor installation and use only All new wiring must be fully verified before applying power Servicing of equipment should be performed by qualified serv...

Страница 2: ...e the entry door may lead to the provided QuickConnect cabling being too short to reach the intended accessory locations 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy O...

Страница 3: ...upancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock Alert Mode Demand Response A V Mode Integration Controls Green Black Red White Adjustable Skylights Sensors Receptacle BMS Out Sw...

Страница 4: ...negative location on the first dimmer terminal block Repeat for additional dimming zones Load 3 Load 2 Load 2 Load 2 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Dimmer 1 Dimmer 2 D...

Страница 5: ...QuickConnect Cable Class 2 QuickConnect Cable Class 2 1 Entry Wallstation Back Connect a QuickConnect cable between the designated wallstation Click Go port on the Room Controller and to one of the Cl...

Страница 6: ...C RJ45 Input Output Device The Input Output Device contains two QuickConnect ports Operating Environment 32 F to 104 F 0 to 40 C For indoor use only Note N The Room Controller connects to standard GG...

Страница 7: ...ach the input output device location 4 3 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy Options Status Reset 0 10V Gain Adjustment Dimmer 3 Dimmer 2 Dimmer 1 0 10V Dimmi...

Страница 8: ...ht sensor for multi zone dimming control in the RC3D and RC3DE models Specifications Voltage 24 VDC supplied from Room Controller Electrical Class 2 LPS Light Sensor Range Low 3 300 lux High 30 3000 l...

Страница 9: ...he daylight sensor to either the Room Controller or to the nearest free input output device QuickConnect Cable Class 2 OCC RJ45 Input Output Device Model OCC RJ45 Occupancy Sensor Coupler Brown Black...

Страница 10: ...Switchpack and the Receptacle BMS Click Go port on the Room Controller SPRC R 20 120 Receptacle Rated Switchpack Click Go Port Line Voltage Wiring to Receptacle s 120VAC Hot Neutral Black White Black...

Страница 11: ...ed wire locations Connect a QuickConnect cable between the Receptacle BMS Out Click Go port on the Room Controller and to one of the ports on the OCC RJ45 ports Press Here Model OCC R J45 Occupancy Se...

Страница 12: ...d Response Default 2 1 1 2 3 4 20 Demand Response 2 1 1 2 3 4 30 Demand Response 2 1 1 2 3 4 40 Demand Response 2 1 If using Demand Response ensure the level of reduction is selected using Energy Opti...

Страница 13: ...eceptact OFF 30 seconds after lighting Alert Mode Overrides system functions to allow for fire alarm emergency or other systems needing to call lighting to a full ON condition Contact Type Required No...

Страница 14: ...get threshold implemented by these advanced energy saving methods Room Controller Networking This section applies to the RC3 PL N RC3D PL N and RC3DE PL N Room Controller models Room Controller Networ...

Страница 15: ...network wiring for shorts to AC ground before connecting to the Room Controller 5 If using Belden 9841 or 89841 ensure shields are taped back and not connected to any metal surfaces 6 Panels and devic...

Страница 16: ...White Orange 277V N Blue Load In Yellow Load 1 Out Red Load 2 Out Purple Load 3 Out Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock...

Страница 17: ...n 1 8 has a value associated with it 1 128 Addresses 1 through 254 are valid for use but 255 all values added together is reserved for system use and should not be used 1 Add the value for each switch...

Страница 18: ...aximum Additional energy savings can be gained by adjusting the trim further if electric lighting contribution is over the target illuminance for the space Locate the position of the trim level adjust...

Страница 19: ...d exit Commissioning Mode press the All OFF button on any wallstation If All OFF is not pressed the controller will save the settings and exit Commissioning Mode after two minutes The setup process is...

Страница 20: ...e window while Zone 3 is the furthest into the space When the remote is used to adjust light levels within the daylight sensor s lens the Red LED should flash each time the button is pressed The Green...

Страница 21: ...low Load 1 Out Red Load 2 Out Purple Load 3 Out 0 10V Dimming Outputs Dimmer 3 Dimmer 2 Dimmer 1 Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac defaul...

Страница 22: ...with the HHPRG RC remote control to indicate that the controller is in Commissioning Mode Under normal operation the daylight sensor LEDs will not flash Quiet Time The LED on the Quiet Time button in...

Страница 23: ...Lights will not turn ON from wallstations Connection Issue Verify that all Click Go Connections are connected to the correct ports for the accessories being used Microprocessor Verify that the Room Co...

Страница 24: ...ve a Quiet Time button ensure that this is not activated Motion sensors are ignored during the 60 minute Quiet Time count down Occupancy Sensor or Time Clock connections are not present To turn lighti...

Страница 25: ...loads go Full ON then resume dimmed level Look in the Daylight Sensor lens to determine if the Green LED is ON fairly steadily If it is the sensor is seeing more daylight than its range will allow Set...

Страница 26: ...itchpacks If still having trouble with receptacle response ON callTechnical Services at 1 800 553 3879 Solatubes will not close Wrong Button Pressed Solatubes close only with certain buttons Make sure...