23

RNNm CNntrNller

 

2.  After lighting is OFF, press the “All OFF” button four times as if you were saying the separated syllables of the word 

“Emergency” {E-MER-GEN-CY}.

3.  The emergency relay will turn ON in response to this command verifying that the emergency load control relay is 

operational.

4.  Once the test is complete, turn OFF the emergency load by pressing the “All OFF” button again.
5.  If left in Test Mode, the Room Controller will automatically exit the emergency test after 1 minute and turn OFF the 

emergency load.

System LED Indicators and Reset Buttons

The Room Controller has an onboard status indicator and reset button to assist with troubleshooting. In addition, other 

components within the Room Controller package have LED indicators that may indicate specific functions.

Room Controller Troubleshooting

Issue

Possible Causes

Suggestions

Lights will not turn ON 

automatically

Vacancy Mode set 

on Room Controller

 

The default mode for occupancy control is Vacancy Mode. Use Energy Option DIP Switch 3 to 

place in Occupancy Mode. In Occupancy Mode, Load 1 (yellow) will trigger automatically upon 

occupancy.

Vacancy Mode 

set on Occupancy 

Sensor

 

If a sensor is being used that has an Automatic/Manual Mode, ensure that the sensor is in 

Automatic Mode.

Connection Issue

 

Verify that all Click & Go Connections are connected to the correct ports for the accessories being 

used.

Lights will not  

turn ON from  

wallstations

Connection Issue

 

Verify that all Click & Go Connections are connected to the correct ports for the accessories being 

used.

Microprocessor

 

Verify that the Room Controller status LED is flashing. If it is flashing, press and release the reset 

button and verify that lighting turns ON for 3 seconds. If there is no response, contact technical 

support.

Power Interruption

 

If the Room Controller status LED is not flashing, check incoming voltage and/or wiring.

Lighting turns  

ON but is not  

the right zone

Wiring

 

Verify that Load 1, Load 2, and Load 3 have been wired to the appropriate loads in the space to 

meet your application.

Emergency lighting 

does not turn ON 

with the correct zone  

(RC3DE only)

Wiring

 

The Room Controller controls the emergency lighting along with the normal lighting Load 1 

(yellow). Ensure that Load 1 (yellow) is connected to the load that the emergency lighting needs to 

operate with.

If still having trNuble with lighting turning ON, call Technical Services at 1-800-553-3879

Lights will not  

remain ON (Lights 

turn OFF approx. 30 

seconds after the On 

command)

The controller  

senses that there is 

an occupancy sensor  

connected but is not  

seeing an occupied  

signal from the 

sensor.

 

Verify that the occupancy sensor LEDs are flashing when motion is occurring.

 

Make sure that the occupancy sensor coupler is connected to the correct wires from the occupancy 

sensor.

 

If the occupancy sensor being used has an Auto/Manual selection, verify that the occupancy 

sensor is in Auto Mode.

 

Verify that you are not using a VAC model sensor.

Содержание Greengate RC3

Страница 1: ...s from more than one power source Designed for indoor installation and use only All new wiring must be fully verified before applying power Servicing of equipment should be performed by qualified serv...

Страница 2: ...e the entry door may lead to the provided QuickConnect cabling being too short to reach the intended accessory locations 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy O...

Страница 3: ...upancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock Alert Mode Demand Response A V Mode Integration Controls Green Black Red White Adjustable Skylights Sensors Receptacle BMS Out Sw...

Страница 4: ...negative location on the first dimmer terminal block Repeat for additional dimming zones Load 3 Load 2 Load 2 Load 2 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Dimmer 1 Dimmer 2 D...

Страница 5: ...QuickConnect Cable Class 2 QuickConnect Cable Class 2 1 Entry Wallstation Back Connect a QuickConnect cable between the designated wallstation Click Go port on the Room Controller and to one of the Cl...

Страница 6: ...C RJ45 Input Output Device The Input Output Device contains two QuickConnect ports Operating Environment 32 F to 104 F 0 to 40 C For indoor use only Note N The Room Controller connects to standard GG...

Страница 7: ...ach the input output device location 4 3 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy Options Status Reset 0 10V Gain Adjustment Dimmer 3 Dimmer 2 Dimmer 1 0 10V Dimmi...

Страница 8: ...ht sensor for multi zone dimming control in the RC3D and RC3DE models Specifications Voltage 24 VDC supplied from Room Controller Electrical Class 2 LPS Light Sensor Range Low 3 300 lux High 30 3000 l...

Страница 9: ...he daylight sensor to either the Room Controller or to the nearest free input output device QuickConnect Cable Class 2 OCC RJ45 Input Output Device Model OCC RJ45 Occupancy Sensor Coupler Brown Black...

Страница 10: ...Switchpack and the Receptacle BMS Click Go port on the Room Controller SPRC R 20 120 Receptacle Rated Switchpack Click Go Port Line Voltage Wiring to Receptacle s 120VAC Hot Neutral Black White Black...

Страница 11: ...ed wire locations Connect a QuickConnect cable between the Receptacle BMS Out Click Go port on the Room Controller and to one of the ports on the OCC RJ45 ports Press Here Model OCC R J45 Occupancy Se...

Страница 12: ...d Response Default 2 1 1 2 3 4 20 Demand Response 2 1 1 2 3 4 30 Demand Response 2 1 1 2 3 4 40 Demand Response 2 1 If using Demand Response ensure the level of reduction is selected using Energy Opti...

Страница 13: ...eceptact OFF 30 seconds after lighting Alert Mode Overrides system functions to allow for fire alarm emergency or other systems needing to call lighting to a full ON condition Contact Type Required No...

Страница 14: ...get threshold implemented by these advanced energy saving methods Room Controller Networking This section applies to the RC3 PL N RC3D PL N and RC3DE PL N Room Controller models Room Controller Networ...

Страница 15: ...network wiring for shorts to AC ground before connecting to the Room Controller 5 If using Belden 9841 or 89841 ensure shields are taped back and not connected to any metal surfaces 6 Panels and devic...

Страница 16: ...White Orange 277V N Blue Load In Yellow Load 1 Out Red Load 2 Out Purple Load 3 Out Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock...

Страница 17: ...n 1 8 has a value associated with it 1 128 Addresses 1 through 254 are valid for use but 255 all values added together is reserved for system use and should not be used 1 Add the value for each switch...

Страница 18: ...aximum Additional energy savings can be gained by adjusting the trim further if electric lighting contribution is over the target illuminance for the space Locate the position of the trim level adjust...

Страница 19: ...d exit Commissioning Mode press the All OFF button on any wallstation If All OFF is not pressed the controller will save the settings and exit Commissioning Mode after two minutes The setup process is...

Страница 20: ...e window while Zone 3 is the furthest into the space When the remote is used to adjust light levels within the daylight sensor s lens the Red LED should flash each time the button is pressed The Green...

Страница 21: ...low Load 1 Out Red Load 2 Out Purple Load 3 Out 0 10V Dimming Outputs Dimmer 3 Dimmer 2 Dimmer 1 Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac defaul...

Страница 22: ...with the HHPRG RC remote control to indicate that the controller is in Commissioning Mode Under normal operation the daylight sensor LEDs will not flash Quiet Time The LED on the Quiet Time button in...

Страница 23: ...Lights will not turn ON from wallstations Connection Issue Verify that all Click Go Connections are connected to the correct ports for the accessories being used Microprocessor Verify that the Room Co...

Страница 24: ...ve a Quiet Time button ensure that this is not activated Motion sensors are ignored during the 60 minute Quiet Time count down Occupancy Sensor or Time Clock connections are not present To turn lighti...

Страница 25: ...loads go Full ON then resume dimmed level Look in the Daylight Sensor lens to determine if the Green LED is ON fairly steadily If it is the sensor is seeing more daylight than its range will allow Set...

Страница 26: ...itchpacks If still having trouble with receptacle response ON callTechnical Services at 1 800 553 3879 Solatubes will not close Wrong Button Pressed Solatubes close only with certain buttons Make sure...

Отзывы: