Reset Daylight Levels
www.eaton.com/lightingsystems
7. Repeat this process for each of the dimming zones as necessary.
8. To save the new levels and exit Commissioning Mode, press the “All OFF” button on any wallstation. If “All OFF” is not
pressed, the controller will save the settings and exit Commissioning Mode after two minutes.
9. The room controller will now operate with the new daylight levels.
1
2
3
4
5
6
Integration Controls
Adjustable Skylight
s
Low En
dH
igh En
d
Energ
y
Options
Statu
s
Reset
0-10V Gain Adjustmen
t
Dimmer 3
Dimmer 2
Dimmer 1
+
-
-
+
+
-
0-10V Dimming
Blue - EM Line In Blue - EM Loads Out
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Black - Line In White/Black - 120V
N
White/Orange - 277V
N
Blue - Load In Ye
llow - Load 1 Out
Red - Load 2 Out Purple - Load 3 Out
0-10V Dimming Outputs
-
+
Dimmer 3
Dimmer 2
Dimmer 1
-
+
+
-
Energy Options DIP Switch
Demand Response Occupancy
Not Used
1 2
3
4
Default 10%
20%
30%
40%
Occ
Vac (default)
Time
Clock
Alert
Mode
Demand
Response
A/V
Mode
+
-
Integration Controls
+
-
+
-
+
Green
Black
Red
White
Adjustable Skylight
s
Sensors
Receptacle
BMS/Out
Switchpack
QuickConnect Cable
s
Sensors
Slider
Station
Wallstations
-
+
-
-
+
+
-
Daylight Gain
Adjustment
Dimmer 3
Dimmer 2
Dimmer 1
0-10V Dimming
Ntee:
N
It is possible to disable daylight dimming for any dimming zone allowing the dimmer to respond only to the raise/lower
controls and wallstation presets. To disable daylight dimming, on the Room Controller, twist the desired dimmer’s gain
adjustment dial fully clockwise, and then fully counter clockwise. When setting daylight levels with the HHPRG-RC
remote, avoid pressing the Zone Level adjustment buttons for the disabled zone. If adjusted in error, simply reset the
gain adjustment dial again.