background image

Lights turn ON at 

a full bright level 

and responds to 

manual dimming 

lower controls but 

do not appear to dim 

automatically from 

daylighting

Daylighting

 

Verify that the daylight sensor is installed in a location that is not obstructed from receiving daylight.

 

Verify that the daylight sensor is properly connected to the Room Controller per the installation 

instructions.

 

Verify that the daylight sensor lens is oriented properly for the location it is installed in.

 

The sensor range may be set too high. If the sensor is located in a darker location, try reducing the 

sensor range to a lower range using the instructions in the Advanced Daylight Level Adjustment 

section.

 

Use the HHPRG-RC remote to adjust daylight levels per the Advanced Daylight Level Adjustment 

procedures in the installation instructions.

 

Check the Low End trimpot to ensure it is not set all the way clockwise.

If still having trNuble with dimmer respNnse ON, call Technical Services at 1-800-553-3879

Receptacle  

switchpacks will  

not turn ON

Alert Mode

 

Alert Mode turns OFF all receptacle switchpacks while the alert is active. Disconnect contact into 

the Alert Mode terminal to verify normal operation resumes. Troubleshoot the connected system to 

determine the cause of the alert signal.

Connection Issue

 

Verify that all Click & Go Connections are connected to the correct ports for the accessories being 

used.

Power Interruption

 

Check incoming voltage and/or wiring to the receptacle switchpack.

Receptacle  

switchpacks will  

not turn OFF

Occupancy Sensor 

or Time Clock  

connections are not 

present

 

To turn OFF, the receptacle switchpacks require either a vacancy command from an occupancy sensor, 

OR a time clock command to After-Hours Mode. Wallstations do not cause receptacles to turn OFF. 

Ensure that one of these methods is being used to successfully integrate receptacle switchpacks.

If still having trNuble with receptacle respNnse ON, call Technical Services at 1-800-553-3879

Solatubes will 

not close

Wrong Button 

Pressed

 

Solatubes close only with certain buttons. Make sure that the button you are pressing should control 

the Solatube. Refer to the Wallstation Operation Charts in your installation instruction for button 

operation details.

Alert Mode

 

Alert Mode opens all Solatubes while the alert is active. Disconnect contact into the Alert Mode 

terminal to verify normal operation resumes. Troubleshoot the connected system to determine the 

cause of the alert signal.

Connection Issue

 

Verify that the Solatube Daylight Dimmer is a supported model and has been connected properly to 

the Room Controller.

Power Interruption

 

Verify incoming voltage and/or wiring to the Solatube daylight dimmer.

Solatubes will not 

open

Wrong Button 

Pressed

 

Solatubes open only with certain buttons. Make sure that the button you are pressing should control 

the Solatube. Refer to the Wallstation Operation Charts in your installation instruction for button 

operation details.

Connection Issue

 

Verify that the Solatube Daylight Dimmer is a supported model and has been connected properly to 

the Room Controller.

Power Interruption

 

Verify incoming voltage and/or wiring to the Solatube daylight dimmer.

If still having trNuble with SNlatube respNnse ON, call Technical Services at 1-800-553-3879

WARRANTIES AND LIMITATION OF LIABILITY

Please refer to 

httpe://www.eatNn.cNm/LightingWarrantyTerms 

for our terms and conditions.

© 2017 Eaton

All Rights Reserved

Printed in USA

Publication No. 9850-000362-04

October 10, 2017

Eaton

1121 Highway 74 South

Peachtree City, GA 30269

P: 770-486-4800

www.eaton.com/lightingsystems

For service or technical assistance:

1-800-553-3879

Canada Sales

5925 McLaughlin Road

Mississauga, Ontario L5R 1B8

P: 905-501-3000-

F: 905-501-3172

Eaton is a registered trademark.

All other trademarks are property  

of their respective owners.

Product availability, specifications, and 

compliances are subject to change 

without notice.

Содержание Greengate RC3

Страница 1: ...s from more than one power source Designed for indoor installation and use only All new wiring must be fully verified before applying power Servicing of equipment should be performed by qualified serv...

Страница 2: ...e the entry door may lead to the provided QuickConnect cabling being too short to reach the intended accessory locations 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy O...

Страница 3: ...upancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock Alert Mode Demand Response A V Mode Integration Controls Green Black Red White Adjustable Skylights Sensors Receptacle BMS Out Sw...

Страница 4: ...negative location on the first dimmer terminal block Repeat for additional dimming zones Load 3 Load 2 Load 2 Load 2 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Load 1 Dimmer 1 Dimmer 2 D...

Страница 5: ...QuickConnect Cable Class 2 QuickConnect Cable Class 2 1 Entry Wallstation Back Connect a QuickConnect cable between the designated wallstation Click Go port on the Room Controller and to one of the Cl...

Страница 6: ...C RJ45 Input Output Device The Input Output Device contains two QuickConnect ports Operating Environment 32 F to 104 F 0 to 40 C For indoor use only Note N The Room Controller connects to standard GG...

Страница 7: ...ach the input output device location 4 3 1 2 3 4 5 6 Integration Controls Adjustable Skylights Low End High End Energy Options Status Reset 0 10V Gain Adjustment Dimmer 3 Dimmer 2 Dimmer 1 0 10V Dimmi...

Страница 8: ...ht sensor for multi zone dimming control in the RC3D and RC3DE models Specifications Voltage 24 VDC supplied from Room Controller Electrical Class 2 LPS Light Sensor Range Low 3 300 lux High 30 3000 l...

Страница 9: ...he daylight sensor to either the Room Controller or to the nearest free input output device QuickConnect Cable Class 2 OCC RJ45 Input Output Device Model OCC RJ45 Occupancy Sensor Coupler Brown Black...

Страница 10: ...Switchpack and the Receptacle BMS Click Go port on the Room Controller SPRC R 20 120 Receptacle Rated Switchpack Click Go Port Line Voltage Wiring to Receptacle s 120VAC Hot Neutral Black White Black...

Страница 11: ...ed wire locations Connect a QuickConnect cable between the Receptacle BMS Out Click Go port on the Room Controller and to one of the ports on the OCC RJ45 ports Press Here Model OCC R J45 Occupancy Se...

Страница 12: ...d Response Default 2 1 1 2 3 4 20 Demand Response 2 1 1 2 3 4 30 Demand Response 2 1 1 2 3 4 40 Demand Response 2 1 If using Demand Response ensure the level of reduction is selected using Energy Opti...

Страница 13: ...eceptact OFF 30 seconds after lighting Alert Mode Overrides system functions to allow for fire alarm emergency or other systems needing to call lighting to a full ON condition Contact Type Required No...

Страница 14: ...get threshold implemented by these advanced energy saving methods Room Controller Networking This section applies to the RC3 PL N RC3D PL N and RC3DE PL N Room Controller models Room Controller Networ...

Страница 15: ...network wiring for shorts to AC ground before connecting to the Room Controller 5 If using Belden 9841 or 89841 ensure shields are taped back and not connected to any metal surfaces 6 Panels and devic...

Страница 16: ...White Orange 277V N Blue Load In Yellow Load 1 Out Red Load 2 Out Purple Load 3 Out Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac default Time Clock...

Страница 17: ...n 1 8 has a value associated with it 1 128 Addresses 1 through 254 are valid for use but 255 all values added together is reserved for system use and should not be used 1 Add the value for each switch...

Страница 18: ...aximum Additional energy savings can be gained by adjusting the trim further if electric lighting contribution is over the target illuminance for the space Locate the position of the trim level adjust...

Страница 19: ...d exit Commissioning Mode press the All OFF button on any wallstation If All OFF is not pressed the controller will save the settings and exit Commissioning Mode after two minutes The setup process is...

Страница 20: ...e window while Zone 3 is the furthest into the space When the remote is used to adjust light levels within the daylight sensor s lens the Red LED should flash each time the button is pressed The Green...

Страница 21: ...low Load 1 Out Red Load 2 Out Purple Load 3 Out 0 10V Dimming Outputs Dimmer 3 Dimmer 2 Dimmer 1 Energy Options DIP Switch Demand Response Occupancy Not Used 1 2 3 4 Default 10 20 30 40 Occ Vac defaul...

Страница 22: ...with the HHPRG RC remote control to indicate that the controller is in Commissioning Mode Under normal operation the daylight sensor LEDs will not flash Quiet Time The LED on the Quiet Time button in...

Страница 23: ...Lights will not turn ON from wallstations Connection Issue Verify that all Click Go Connections are connected to the correct ports for the accessories being used Microprocessor Verify that the Room Co...

Страница 24: ...ve a Quiet Time button ensure that this is not activated Motion sensors are ignored during the 60 minute Quiet Time count down Occupancy Sensor or Time Clock connections are not present To turn lighti...

Страница 25: ...loads go Full ON then resume dimmed level Look in the Daylight Sensor lens to determine if the Green LED is ON fairly steadily If it is the sensor is seeing more daylight than its range will allow Set...

Страница 26: ...itchpacks If still having trouble with receptacle response ON callTechnical Services at 1 800 553 3879 Solatubes will not close Wrong Button Pressed Solatubes close only with certain buttons Make sure...

Отзывы: