Connecting the Occupancy Sensor to the Room Controller
www.eaton.com/lightingsystems
Wall/Corner Mounting
30’
30’
OAWC-DT-120W &
OAWC-P-120W
Mounting
Base
Low Voltage
Wires
Wall Board
Occupancy Sensor Mounted to Wallboard
Sensor
OAWC sensors can be mounted to the ceiling, junction box
or round fixture with raceway. Optimum mounting height is
8-10 feet.
DN nNt mNunt Nver 12 feet.
Mount at fixture height to avoid obstucting view.
Mount the sensor at least 4-6 feet from air supply ducts to
avoid false activation.
Ntee:
N
Occupancy sensors can also be mounted to an
octagon box or round fixture with raceway.
Mounting
Base
Mounting Cover
Screw, Nut and Washer
Drop Ceiling
Low Voltage Wires
Occupancy Sensor Mounted to Wallboard
Sensor
Connecting the Occupancy Sensor to the
Room Controller
Up to two occupancy sensors may be powered from the
Room Controller. Sensors connect using the provided
OCC-RJ45 Input/Output Device and QuickConnect Cables to
ports 3 or 4 on the Room Controller.
Once the sensor is mounted, attach the OCC-RJ45 Input/
Output Device to the sensor leads matching the wire
colors to the label on the input/output device as shown.
Connect the Input/Output Device to one of the two sensor
ports on the Room Controller. Use the shortest lengths of
QuickConnect cable from your QuicKit that will reach the
input/output device location.
4
3
1
2
3
4
5
6
Integration Controls
Adjustable Skylights
Low End
High End
Energy Options
Status
Reset
0-10V Gain Adjustment
Dimmer 3
Dimmer 2
Dimmer 1
+
-
-
+
+
-
0-10V Dimming
0-10V Dimming Outputs
-
+
Dimmer 3
Dimmer 2
Dimmer 1
-
+
+
-
Blue - EM Line In Blue - EM Loads Out
CAUTION: Bonding between conduit connections is not automatic and must be provided as part of the installation.
Black - Line In White/Black - 120V N White/Orange - 277V N
Blue - Load In Yellow - Load 1 Out
Red - Load 2 Out Purple - Load 3 Out
Energy Options DIP Switch
Demand Response Occupancy
Not Used
1 2
3
4
Default 10%
20%
30%
40%
Occ
Vac (default)
Time
Clock
Alert
Mode
Demand
Response
A/V
Mode
+
-
Integration Controls
+
-
+
-
+
-
Green
Black
Red
White
Adjustable Skylights
Sensors
Receptacle
BMS/Out
Switchpack
QuickConnect Cables
Sensors
Slider
Station
Wallstations
1
2
3
4
Vacancy Mode
(Default)
4
3
1
2
3
4
Occupancy Mode
All Relays On 50%
1
2
3
4
Occupancy Mode
All Relays On to
daylight level *
* Dip Switches 3&4 up triggers programmable Scene 6, which
can be adjusted using the Personal Remote (HHPR-RC)
4
3
4
3
QuickConnect Cable
(Class 2)
Connect a QuickConnect cable between one of
the two Sensor Click & Go ports on the Room
Controller and to one of the Click & Go ports
on the OCC-RJ45 Input/Ouput Device.
OCC-RJ45
(Input/Output Device)
Model: OCC-RJ45
Occupancy Sensor Coupler
Brown
Black
Red
Blue
Ntee:
N
For spaces that need more than two occupancy
sensors see the app note: “
Room Controller
applications for additional occupancy sensors,”
on our
website.