Section D - Configuration, cont’d.
FIG. D50
3. Three Comfort Zones
To configure three units, ZONES need to be established.
Refer to Section 2.3A and 2.3B for Zone 1 and Zone 2
configuration.
115 V AC must be to ZONE 3 unit. A communication line
must be between ZONE 2 and ZONE 3 units.
Configure ZONE 3 unit the same as other
like
units,
EX-
CEPT
for the Dip switches. Dip switch 4 (ZONE 3) to ON
position, and all other Dip switches to OFF position.
4. Four Comfort Zones
To configure three units, ZONES need to be established.
Refer to Section 2.3A, 2.3B and 2.3C for Zone 1, Zone 2
and Zone 3 configuration.
115 V AC must be to ZONE 4 unit. A communication line
must be between ZONE 3 and ZONE 4 units.
Configure ZONE 4 unit the same as other
like
units,
EX-
CEPT
for the Dip switches. Dip switch 3 (ZONE 4) to ON
position, and all other Dip switches to OFF position.