Section D - Configuration, cont’d.
One Rooftop Heat Pump Plus One Rooftop Air Conditioner
Plus Two Gas Furnaces
To configure one rooftop heat pump plus one rooftop air
conditioner plus two gas furnaces, ZONES need to be es-
tablished. For explanation purposes, the front unit (heat
pump) and one furnace will be Zone 1; and the rear unit
(air conditioner) and one furnace will be Zone 2. Zones
can be arranged per the customer’s wishes.
EACH air conditioner must have 115V AC. Only one air
conditioner requires 12V DC. Communications line must
be between the Comfort Control Center and ONE unit only.
A second communications line must be connected between
the two units control boxes.
Two (2) furnace thermostat wires must be between front
unit and front furnace. Two (2) furnace thermostat wires
must be between rear unit and rear furnace.
For explanation purposes the 12V DC, Comfort Control
Center communications line and the two (2) furnace ther-
mostat wires from front furnace are to ZONE 1 (front) unit.
The two (2) furnace thermostat wires from rear furnace
are to ZONE 2 (rear) unit.
ZONE 1 (heat pump) configuration should have all Dip
switches to OFF position. The cold (freeze) control is
NOT used and P5 (blue) connector should remain open.
The ambient sensor should connect into P3 (red) con-
nector.
FIG. D47
ZONE 2 (air conditioner) configuration should have Dip
switch 5 (ZONE 2) to ON position and all other Dip
switches to OFF position. The cold (freeze) control
should be plugged into P5 (blue) connector. The re-
mote sensor (if used) must be plugged into P4 (white)
connector.
FIG. D48
Note:
If a remote sensor is used, it must be plugged into
the P4 (white) connector.
Improper connections can cause component
damage.
FIG. D49