Section C - Components, cont’d.
C16. Relays
C16a.
Time Delay Relay
The time delay relay is used on Model
39424.601
. Its pur-
pose if to provide a thirty second delay of power to Circuit 2
System after Circuit 1 System. To check the relay, use a
voltmeter. Place one lead of voltmeter to Terminal 1 of re-
lay. Thirty seconds after Terminal 1 receives AC volts, move
voltmeter lead to Terminal 2 of relay. AC volts should be
present.
FIG. C22
C16b.
Relay, SPST (single pole/single
throw) used on Models
39224.601 and 39424.601.
On Model
39224.601
, it is used to complete the 115 volt
AC circuit to the compressors, high fan and low fan. On
Model
39424.601
, it is used to complete 115 volt AC to the
reversing valves for Circuit 1 and Circuit 2.
The relay has a DC volt coil. The coil terminals are 1 and 3.
When the coil is NOT energized (no power to terminals 1
FIG. C23
and 3), no continuity will exist between terminals 4 to 2.
When the coil is energized (power to terminals 1 and 3),
continuity will exist between terminals 4 to 2.
C16c.
Relay, SPST (single pole/single
throw) is used on Models
39115.602, 39115.616 and
39115.626.
On these models it is used to complete 115 volt AC circuits
to the compressor and for fan speeds.
The relay has a DC volt coil. To check the relay, first verify
AC volts have been turned off to the unit.
Next, verify the relay coil is NOT energized (no DC power).
No continuity should exist between terminals COM to NO.
Energize the coil with DC volts (10 to 16). Continuity should
exist between terminals COM and NO. If the above checks
are correct, the relay is good - DO NOT replace it. If the
previous checks are not correct, the relay is defective and
should be replaced.
FIG. C24
C16c.
Relay, SPDT (single pole/
double throw) is used on
Models 390XX.XXX.
Controls the fan motor.
The relay has a 24 volt AC coil. To check the relay, first
verify all AC volts have been turned off to the unit.
Next, remove the wires from COM and NC terminals. Verify
the relay coil is not energized (no AC power). Continuity
should exist between terminals COM and NO. Next, ener-
gize the relay coil with 24 volts AC. Continuity should exist
between terminals COM and NO and no continuity between
COM and NC. If the above checks are correct the relay is
good - DO NOT replace it. If the above checks are not
correct, the relay is defective and should be replaced.