dormakaba ED50 Installation Instructions – Fine cover
Chapter 20
20.2.2 Active door, set parameters dL and Ad.
1. Set active door program switches to CLOSE.
2. Set parameters dL (door type) and Ad (caster angle )
for active door.
• Castor angle sets opening angle of active door
before inactive door starts to open.
Factory setting is 30°.
Step 1
Press
Press and hold PRG > 3 s to enter
program mode, AS parameter
displayed.
Step 2
Press
Scroll to
dL
parameter.
Step 3
Press
Displays "00" , factory setting.
Step 4
Press
"00" starts flashing.
Step 5
Press
Scroll to select parameter value
("1" as an example).
Step 6
Press
Saves value entered. Display stops
flashing.
Step 7
Press
Returns to door type parameter.
Step 8
Press
Scroll to Ad parameter.
Step 9
Press
Displays "30", factory setting.
Step 10
Press
Scroll to select parameter value
(10° as an example).
Step 11
Press
Saves value entered. Display stops
flashing.
Step 12
Press
Returns to caster angle parameter.
Step 13
Press
Exits program mode. Operator is ready
for operation.
Fig. 23.2.2 Program switches in
CLOSE position
Door type
Parameter
value
Parameter description
0*
Single door
1
Double door, with astragal.
Active door operator, door opens first.
2
Double door, with astragal.
Inactive door operator.
3
Double door, without astragal.
Active door operator. Both doors open
simultaneously.
4
Double door, without astragal.
Inactive door operator. Both doors open
simultaneously.
*
Factory setting
CAUTION
Full width cover option
.
Single program switch located on inactive
door.