71
ED50
01-2020
DL4615-001
dormakaba ED50 Installation Instructions – Fine cover
Chapter 20
Step 1
Press
Press and hold PRG > 3 s to enter
program mode, AS parameter
displayed.
Step 2
Press
Scroll to
dL
parameter.
Step 3
Press
Displays "00" , factory setting.
Step 4
Press
"00" starts flashing.
20.2.3 Inactive door, set parameter dL.
1. Set program switch to CLOSE.
2. Set parameter dL (door type) for inactive door.
Step 5
Press
Scroll to select parameter value
("3" as an example).
Step 6
Press
Saves value entered. Display stops
flashing.
Step 7
Press
Returns to door type parameter.
Step 25
Press
Exits program mode. Operator is ready
for operation.
20.3 Connect communication cable between operators
Fig. 20.3.1 Double door operators, communication cable
1
RJ45 jack
(horizontal) for
communication
cable
2
Communication
cable DX3485
2
Communication
cable DX3485
3
RJ45 plug
Fig. 20.3.3 Communication cable
20.3.1 Communication cable DX3485
lengths.
• DX3485-010 – 250 mm, 9 7/8"
• DX3485-020 – 1030 mm, 40 1/2"
• DX3485-030 – 2030 mm, 79 15/16
20.3.2 Install communication cable.
1. Set program switch to CLOSE.
2. Connect communication cable to active
and inactive operator RJ45 jacks.
3. Secure cable to header.
20.3.3 Test door operation.
1. Set program switch to AUTO.
2. Test double door operation.
• Use knowing act device.
Fig. 20.3.4 Program switch
1
Program switch,
3 position
1
2
3
3
1
4
Fig. 20.3.2 RJ45 jack
1
RJ45 jack
4
Program switch
cable
1
1
2