Installation
Technical Manual
66
V28 - 08/2019
Electronic safe lock
When a micro switch is connected to input 2 and the closed micro switch indicates the status
"door open", both checkboxes "Invert input (open contact to trigger)" and "door contact"
must be selected in AS284-USBW or AS284-NETW programming software for a smooth op-
eration.
It is possible to connect additional external signals to the lock terminal block.
It is possible to change the function and polarity of inputs and outputs with AS284-USBW or
AS284-NETW programming software.
1
2
3
4
5
6
7
8
IN2
GND
IN1+
IN1-
OUT1 A
OUT1 B
OUT2 A
OUT2 B
Terminals
Description
Unit
Remarks
1/2
Output 2
Factory setting: lock open (OR
Boolean operation with bolt,
motor or door open)
30VDC/2A
Relay with potential-free
working contacts NO
(normally open). Contact
is open when lock is
closed.
3/4
Output 1
Factory setting duress alarm
50VAC/0.5A
with resistive
load
Relay with potential-free
working contacts NO
(normally open). Contact
is closed when duress
alarm is activated.
5(-)/6(+)
Input 1
Factory setting not assigned
Optional: remote disabling or
controlled disabling
9 ...18VDC (mini-
mum 13mA and
maximum
20mA)
7/8
Input 2
Factory setting: not assigned,
configurable via AS284-USBW
or AS284-NETW programming
software
Optional:
•
Door contact
•
Skip Time Delay
•
Time Locking Interruption
and
•
external input event A - F
Potential-free
contact
Do not apply any voltage,
potential-free contact
only.
Use a suitable micro
switch with gold-plated
contacts
12VDC/50mA (e.g. DB se-
ries by Cherry).
If input 2 is assigned as
"door contact" and not
inverted, an open switch
contact is used as "door
open".
The bolt is as long open as
terminals 7 / 8 are electri-
cally disconnected.