dormakaba ED50/ED100/ED250 OHC Header
Setup and Troubleshooting Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Static force in closing direction
ED50: Low energy only.
ED100/ED250: can be configured for full energy using Parameter F2.
• Static force in closing direction (basic parameter for wind load control).
• Static force on door closing edge can be changed using this parameter.
• After parameter adjustment, internal monitoring system checks if parameter setting
is admissible. If setting exceeds admissible value, the setting is alternately displayed
with the permissible value.
1. After parameter set, verify setting meets ANSI/BHMA standards. See Chapter 19.
17
Low Energy
ANSI/BHMA A156.19
Parameter
setting *10
20 N - 6 0 N
4.5 lb f - 13.5 lb f
6
Full Energy
ANSI/BHMA A156.10
Parameter
setting *10
20 N - 130 N
4.5 lb f - 29.8 lb f
6
Motor driven latching action, automatic
mode
• System offers a motor driven latching action in automatic mode in addition to
mechanical latching action.
• Static force in opening direction (basic parameter for wind load control).
• Low energy operator (ANSI/BHMA A156.19): static force range is reduced.
• The
EP
parameter setting is designed to increase static force on door closing edge to
insure proper closing despite resistance caused by door seals or locking devices.
1. After
EP
parameter set, verify setting meets ANSI/BHMA standards. See Chapter 19.
• After parameter adjustment, internal monitoring system checks if parameter setting
is admissible. If setting exceeds admissible value, the setting is alternately displayed
with the permissible value.
2. Setting should be increased step by step from a low setting so as to avoid damage
to the system. Use the lowest possible setting.
3. Ensure that both the door itself and the push or pull arm installation are suitable for
the additional, permanent forces.
19
0 - 9
0
Motor driven latching action angle
Door opening angle at which motor driven latching action
EP
is activated.
• Starting angle of the latching angle adjustable from 10°.
20
2 -10
°
3
Keep closed force
21
0 - 9
0
0
Off
1
to
9
• Keep closed force can be set from 0 (off) to 9, maximum force.
• Keep closed force is:
• Permanently applied following motor drive latching action.
• Designed to keep door in closed position even if wind acts on door.
Push & Go
22
0 - 1
0
0
Off
1
• Door close mode parameter
hd
must be set to "0" (automatic) to enable this
function.
1. When set to 1, parameter is activated.
• Automatic opening of door is started when door is manually moved 4° out of
the closed position.
A.1.1 Driving parameters detail.