59
ED50/ED100/ED250
09-2021
DL4617-003
dormakaba ED50/ED100/ED250 OHC Header
Setup and Troubleshooting Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Status relay function, X7 terminals
0
Status relay is deactivated.
27
0 - 6
1
1
Status relay activated as soon as door reaches door "closed" position.
2
Status relay activated as soon as door reaches door "open" position.
3
Status relay activated when error codes are displayed on 2 digit operator display.
4
"Door closed and locked" activates status relay.
5
Status relay activated when information or error codes are displayed on 2 digit
operator display.
6
• Status relay activated when door is opened further than opening angle
parameter
OA
, set during learning cycle.
• Parameter
OA
value can only be changed using dormakaba handheld or by
performing another learning cycle.
Locking device output configuration;
output X3, 1G (24V) and input X6, 4/4a
Reference Chapter 8.
28
0 - 1
0
0
Locking device output terminal X3, 1G (24V) is independent of Input X6, 4/4a.
1
• Locking device output terminal X3, 1G (24V) is turned on as soon as contact at
X6, 4/4a is opened..
• Terminal X3, 1G 24V output is on for as long as contact at X6, 4/4a is open,
motor lock with a 100% duty factor is required.
• This function is not available for DCW motor locks.
Cycle counter
• Total number of opening and closing cycles displayed is shown in increments of
10000; Display value, "4", 40,000 cycles, Display value, "53", 530,000 cycles.
• Total number of cycles can be displayed on dormakaba handheld.
• A display value of "99" means 990,000 cycles or greater.
29
0 - 99
*
10000
cycles
Delete error log
30
0 - 1
0
0
No function.
1
1. When "1" entered, Error log is deleted.
• Parameter is then automatically reset to "0".
Reset service interval display,
operator yellow LED
31
0 - 1
0
0
No function.
1
1. When "1" entered:
• Service cycle counter is reset to 200,000.
• Service interval is reset to 12 months.
• Yellow LED not illuminated.
• Parameter is then automatically reset to "0".
• Values other than default values must be set using dormakaba USA, Inc.
handheld:
• Maintenance interval
• Maintenance cycles
A.1.1 Driving parameters detail.