62
ED50/ED100/ED250
09-2021
DL4617-003
dormakaba ED50/ED100/ED250 OHC Header
Setup and Troubleshooting Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Upgrade card barrier-free toilet
1. Once upgrade card installed, parameter value will automatically change to 1
(upgrade card installed, function not activated).
2. Activate function by changing parameter
F7
to 2.
3. Operator power reset is required; turn power switch off, wait 10 s and turn power
back on.
• Upgrade card assigns inputs and outputs of the control unit with functions which are
required for this application.
43
Available
upgrade card
codes
(Para. A1.1.1)
0, 1,
2, 3
0
Upgrade card DCW
1. Activate function by installing upgrade card, parameter value will automatically
change to 2.
• Upgrade card provides operator with DCW bus connection.
• Plug for terminal board X8 socket included with upgrade card.
• DCW bus enables connection of:
• Program switch EPS DCW (max. 2)
• Motor lock controls SVP-S 2x DCW (max. 2)
• Motor lock SVP 2000 (max. 1)
• RM-ED lintel mounted smoke detector
• Key switch button ST 32 DCW (max. 2)
• I/O module DCW (max. 1)
44
Available
upgrade card
codes
(Para. A1.1.1)
0, 2, 3
0
COM 1 configuration interface
45
0 - 1
0
0
Interface programmed for communication with dormakaba handheld.
1
Interface programmed for use with dormakaba TMS Soft control software.
Backcheck when door opened manually
• Angle after which door is braked when manually opened.
• Back check level is automatically optimized during manual door opening cycles.
• bc
function improves door braking behavior in end position so door does not move
beyond set opening angle
OA
1. Entered
bc
value is subtracted from set opening angle
OA
, example:
• Opening angle, 90°:
Parameter
bc
, 12°, door back check starts at 78°.
46
5 - 40
(v1.9)
°
10
Door thickness
1. Enter parameter
Td
in mm.
• Door thickness affects measured door opening angle.
• Parameter
Td
enables a more accurate door width to be entered, if required.
47
0 - 99
mm
35
Td
0 -
3 7/8"
1 3/8"
Deactivation of drive; X6, 4 and 4a, trigger
type
48
0 - 1
0
0
NC contact, drive function is deactivated when NC contact is open.
1
NO contact, drive function is deactivated when NO contact is closed.
Night-bank contact X1; 3 and 35, trigger
type
49
0 - 1
0
0
1. NO contact, night-bank function is triggered when NO contact is closed.
• Typically used when using a key switch or an access control system.
1
1. NC contact, night-bank function is triggered when NC contact is opened.
• Typically used when connected to building management system to trigger
doors (signal normally present).
A.1.1 Driving parameters detail.