dormakaba ED50/ED100/ED250 OHC Header
Setup and Troubleshooting Instructions
Chapter 15
15 Pair door parameters, Sync cable
15.1 Set ED operator parameters for pair door operation
15.1.1 Active door, set parameters dL and Ad.
1. Set Mode switch to CLOSE.
2. Set parameters
dL
(door type) and
Ad
(castor angle )
for active door.
• Castor angle sets opening angle of active door
before passive door starts to open.
Factory setting is 30°.
Door type
Parameter
value
Parameter description
0*
Single door
1
Pair door, with astragal.
Active door operator, door opens first.
2
Pair door, with astragal.
Passive door operator.
3
Pair door, without astragal.
Active door operator. Both doors open
simultaneously.
4
Pair door, without astragal.
Passive door operator. Both doors open
simultaneously.
*
Factory setting
Step 1
Press
Press and hold right button greater
than 3 seconds to enter program
mode, AS parameter displayed.
Step 2
Press
Scroll to
dL
parameter.
Step 3
Press
Displays "00" , factory setting.
Step 4
Press
"00" starts flashing.
Step 5
Press
Scroll to select parameter value
("1" as an example).
Step 6
Press
Saves value entered. Display stops
flashing.
Step 7
Press
Returns to door type parameter.
Step 8
Press
Scroll to
Ad
parameter.
Step 9
Press
Displays "30", factory setting.
Step 10
Press
Scroll to select parameter value
(10° as an example).
Step 11
Press
Saves value entered. Display stops
flashing.
Step 12
Press
Returns to caster angle parameter.
Step 13
Press
Exits program mode.
Fig. 15.1.1 Mode switch
NOTICE
If using BEA LZR Microscan,
dL
parameter must
be "0" for each door.
CAUTION
Both doors must have full learning cycles
completed; reference Chapter 12.
Close