24.7.12
Instruction manual LOCON 24, 48, 64, LTC, TERM 24 and TERM 6 V. 8.8
105
Deutschmann Automation GmbH & Co. KG
Appendix
20 Appendix
20.1 Description and connection of the DICNET
®
-Adapter
20.1.1
DICNET
®
-Adapter DICADAP 3
The DICNET-Adapter serves to connect a PC to a DICNET-network of the company
DEUTSCHMANN AUTOMATION.
It converts both the network protocol as well as the physical RS485-signals, so that a PC with the
WINDOWS-software "WINLOC" will be in the position to communicate with those control units
from DEUTSCHMANN AUTOMATION, existing in the net through a serial interface (COMx).
"WINLOC" is able to run under WIN 3.1x, WIN95/98 and WIN NT. The basic version is available
free of charge.
The DICNET-Adapter is directly connected to a serial interface of the PC through the 9-pin D-
SUB plug.
On the other side of the adapter (25-pin D-SUB plug) the DICNET-Bus and the supply voltage,
which is allowed to range between 10V and 30V, is fed according to the below pin-assignment.
In case the DICNET-Adapter is connected as the last subscriber in the bus, the internal bus-ter-
minating resistor has to be activated by means of bridges of the PIN's with R+ and
DICNET- with R-. (More detailed information to the bus-termination and to the connection to the
DICNET can be found in the instruction manual of the used control unit.)
Pin assignment 25-pin:
1-15
Reserved (do not wire)
16
R+
17
18
DICNET -
19
R-
20-23 Reserved (do not wire)
24
+24 V
25 GND
Pin assignment 9-pin:
2
Rx
3
Tx
5
GND
Others nc