Operation via TERM 24
Deutschmann Automation GmbH & Co. KG
80
Instruction manual LOCON 24, 48, 64 , LTC, TERM 24 and TERM 6 V. 8.8
24.7.12
Please note that the programmed switch-off delay time of 123 ms (in this
example) which is started with each leading edge
has an even higher
priority than the result of the logic operation, i.e. the output remains at 24
V if the delay time has not yet elapsed even if the logic operation would
deactivate the output.
14.6.6
Graphical illustration of example 1
Picture 11: Example, logic operation
14.6.7
Example 2
Here is an example whose result causes output 8 to blink:
14.6.8
Cycle time of the units with logic function
The cycle time of LOCON units with logic function increases by 300 µs + 10 µs per logic opera-
tion.
The logic functions can also be programmed with the WINLOC software.