Operation via TERM 24
Deutschmann Automation GmbH & Co. KG
74
Instruction manual LOCON 24, 48, 64 , LTC, TERM 24 and TERM 6 V. 8.8
24.7.12
14.4.6
Speed scaling
X00 L32 PA000
Speed Scal: 0060
Please refer to the parameter table of the connected cam control for details.
14.4.7
Fictitious encoder value (Gear factor)
Regardless of the resolution of the encoder actually connected, it is possible to program a "ficti-
tious encoder resolution", thus allowing you to implement an electronic transmission. If, for
example, you use an encoder with a real resolution of 360 increments per revolution and one full
revolution corresponds to a traverse distance of 1,000 mm, you must enter a "fictitious resolu-
tion" of 1,000 increments in order to program the cam control in "mm".
X00 L32 PA000
Fict. Res.: 00360
The default value corresponds to the resolution of the encoder connected. When all changes
have been made and confirmed, you can quit the menu with
.
The changed parameters are only accepted by the LOCON when the menu is quit with
.
You can abort the initialisation menu at any time with key
. Values already
changed are accepted. Sub-menu items which are not to be changed can be skipped by
pressing keys
once. Please refer to chapter "Parameter description"
for the connected cam control for a description and value ranges for the individual
parameters.
14.5 Configuration
Starting from the main menu, you can choose the Configuration menu by pressing key
se-
veral times.
I00 L48 PA000
CONFIGURATION
Should you move one menu item too far, you can return with key
or you can press key
to move directly back to the main menu.
Pressing key
accepts the chosen menu item; you can scroll through the parameters with
or
.