HyCassette-Geko
Hydraulic Connection
PR-2015-0159-GB • Subject to modifications • R1-11/2015
59
5.4.2 Medium connection in a 2-pipe system
•
At the beginning of the fitting procedure, remove caps on the water inlet and
outlet pipes.
•
Fit the connections while ensuring they are free of mechanical stress.
•
Mount the lateral drain pan as described in "Mounting lateral condensate
pan" on page 65.
2-pipe system with 2-way valve
2-pipe system with 3-way directional control valve
RISK OF DAMAGE TO THE UNIT!
During fitting, the connecting nut on the heat exchanger must be countered with
a pipe wrench.
Pos. 1:
Valve actuator motor
Pos. 2:
Inlet line
Pos. 3:
Return line
Pos. 4:
Lateral condensate pan
Pos. 5:
Shut-off valve or ball valve (optional, de-
pends on unit version)
Fig. 5-7:
2-way valve in a 2-pipe system
Pos. 1:
Valve actuator motor
Pos. 2:
Inlet line
Pos. 3:
Return line
Pos. 4:
Lateral condensate pan
Pos. 5:
Shut-off valve or ball valve (optional, de-
pends on unit version)
Fig. 5-8:
3-way valve in a 2-pipe system
4
1
2
3
5
4
1
2
3
5