6.12.6 Network set up MATRIX.Net
Data transfer cable
When building up the MATRIX.Net, only use data transfer cables according to
DIN 19245 T3, with twisted wires pairs and with braided shielding. (See tab. 6-4)
We recommend the following data transfer cable:
Line lengths
Regardless of the cross-section and the number of users, the maximum line
length including branch feeders must not exceed 600 m.
Total max. line
length [m]
Max. line length
with branch feeders
[m]
Manufacturer
Cable type
Only
MATRIX.Net
MATRIX.Net +
supply voltage
50
50
LAPP cable
UNITRONIC
®
BUS CAN
1x2x0.22
2x2x0.22
300
150
LAPP cable
UNITRONIC
®
BUS CAN
1x2x0.34
2x2x0.34
600
150
LAPP cable
UNITRONIC
®
BUS CAN
1x2x0.5
2x2x0.5
30
30
LAPP cable
UNITRONIC
®
BUS LD
1x2x0.22
2x2x0.22
30
30
LAPP cable
UNITRONIC
®
Li2YCY (TP)
2x2x0.22
150
60
LAPP cable
UNITRONIC
®
Li2YCY (TP)
1x2x0.34
2x2x0.34
150
60
LAPP cable
UNITRONIC
®
Li2YCY (TP)
1x2x0.5
2x2x0.5
30
30
LAPP cable
UNITRONIC
®
Li2YCY PiMF
2x2x0.22
300
150
LAPP cable
UNITRONIC
®
Li2YCY PiMF
2x2x0.34
600
150
LAPP cable
UNITRONIC
®
Li2YCY PiMF
2x2x0.5
50
50
HELUKABEL
CAN BUS
1x2x0.22
4x1x0.22
300
150
HELUKABEL
CAN BUS
1x2x0.34
4x1x0.34
600
150
HELUKABEL
CAN BUS
1x2x0.5
4x1x0.5
30
30
HELUKABEL
PAAR-TRONIC-Li-2YCYV
2X2X
2x2x0.22
30
30
BELDEN
9841
1x2xAWG24
30
30
BELDEN
9842
2x2xAWG24
150
60
BELDEN
3105A
1x2xAWG22
150
60
BELDEN
3107A
2x2xAWG22
Tab. 6-4:
Data transfer cable