40.
Loosen the four nuts of the fan suspension with a socket set, one by one
and crosswise. They are located above the fan impeller. You get access to
the nuts through the assembly holes in the fan impeller. Spin the impeller
to the right position. The bolts are torsion-proof. It is not necessary to apply
counter-pressure. While doing so, hold the fan with the other hand.
Remember the installation position of the fan for the assembly. (See Fig. 8-
9).
41.
Lower the fan carefully till it hangs on the provisional cable strap. While
doing so, thread the cable sleeve out of the heat exchanger connection
plate (see Pos. 2 in Fig. 8-7). Make sure that the cables are not under ten-
sion.
42.
Now you can clean and disinfect the inner surfaces of the casing above the
fan with a wet cloth.
43.
Wipe off any contamination on the fan impeller. Disinfect fan impeller with
a cloth. Spin impeller to reach certain parts easier.
Fig. 8-8:
Provisional fastening of the fan
Fig. 8-9:
Dismantling fan
RISK OF DAMAGE TO THE UNIT!
Do not spray disinfectant or other liquids on the fan.