Commissioning
HyCassette-Geko
113
PR-2015-0159-GB • Subject to modifications • R1-11/2015
7.9.1 Checking control cables
The data/commands are communicated via control cables. Depending on the unit
equipment, these should be connected or checked in accordance with the wiring
diagram affixed to the unit connection box ( seeConnecting control cables on
page 76).
The yellow LED on the unit PCB signals active power supply to the electronics.
•
If the LED is off, check the 230 V power supply on the unit.
7.9.2 Checking data connection
Data are communicated via a 2/4-wire data cable. This cable must be connected
and/or checked in accordance with the wiring diagram attached to the unit con-
nection box (see Completing bus connection on page 76).
Three LEDs on the unit printed circuit board signal the operating status of the unit.
7.10 Checking control inputs
The MATRIX 3500 control systems are fitted with control inputs
Consider the factory-performed configuration for checking control inputs and out-
puts.
Refer to the unit connection diagram (attached to the connection box) for the rel-
evant controller function.
Changes to the configuration carried out by others on-site (via MATRIX.PC ser-
vice software) have to be considered separately.
MATRIX
3500
✓
MATRIX
3500
✓
LED
LED
status
Operating status
ACTION
Yel-
low
On
Power supply to electronics OK
–
Off
Power supply to electronics not OK
Check 230 V power supply for the unit
gree
n
On
Operating system and controller software
have been started and are working prop-
erly
–
Off
Faulty software or processor
Replace PCB
Red
Continu-
ously on
Error in electronics
De-energize PCB and wait for a short time. Pow-
er the PCB on again. If the error message is still
active, replace the PCB.
Flashes
Data bus interruption
Examine the connection of the data lines and the
setting of the terminating resistances at all devic-
es.
Tab. 7-4:
Operation status and troubleshooting of the data connection (MATRIX 3500)