![Denco HyCassette-Geko Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/denco/hycassette-geko/hycassette-geko_operation-manual_2480034021.webp)
HyCassette-Geko
Technical Description
PR-2015-0159-GB • Subject to modifications • R1-11/2015
21
2.5
Unit data
2.5.1 Unit weight and water charge of heat exchanger
2.5.2 air volume flow
Unit type
Capacity
size
Weight [kg]
Water charge[l]
2-pipe
4-pipe
2-pipe
4-pipe
Heating
Cooling
SWIRL
®
0
29
31
1.8
1)
1.5
2)
0.4
2.1
1)
1.7
2)
1
31
31
2.3
0.4
1)
0.6
2)
2.1
1)
1.7
2)
2
32
31
3.1
0.4
1)
0.6
2)
2.1
1)
1.7
2)
3
30
-
2.3
-
-
4
32
-
3.1
-
-
4-way
0
28
30
1.8
1)
1.5
2)
0.4
1)
0.6
2)
2.1
1)
1.7
2)
1
30
30
2.3
0.4
1)
0.6
2)
2.1
1)
1.7
2)
2
31
30
3.1
0.4
1)
0.6
2)
2.1
1)
1.7
2)
3
29
-
2.3
-
-
4
31
-
3.1
-
-
1) without electric heater
2)
with electric heater
Tab. 2-8:
Unit weight and water charge of heat exchanger
Unit
type
Motor
configuratio
n
Capacity stage
Air volume flow [m
3
/h]
2-pipe
4-pipe
Fan stages 1)
1
2
3
4
5
SWIRL
®
AC
0
0
210
250
380
-
-
1
1
270
390
530
-
-
2
-
250
360
500
-
-
3
2
410
580
670
-
-
4
-
390
550
640
-
-
EC
1
1
210
270
390
530
670
2
-
210
250
360
500
640
4-way
AC
0
0
250
310
460
-
-
1
1
330
480
660
-
-
2
-
310
450
620
-
-
3
2
480
710
850
-
-
4
-
480
710
830
-
-
EC
1
1
250
330
480
660
850
2
-
250
310
450
620
830
1)
Stage operation of EC motors only in connection with a suitable stage operation, otherwise continuous operation.
Tab. 2-9:
Air volume flow