![Denco HyCassette-Geko Скачать руководство пользователя страница 77](http://html1.mh-extra.com/html/denco/hycassette-geko/hycassette-geko_operation-manual_2480034077.webp)
HyCassette-Geko
Electrical Connection
PR-2015-0159-GB • Subject to modifications • R1-11/2015
74
6.9
DencoHappel MATRIX control electronics
6.10
Mounting control panel
All IP20 control panels have an integrated room temperature sensor. The latter
can be used when the control panel is mounted at an optimum indoor location for
regulating temperature. All IP54 control panels are supplied with a separate exter-
nal room temperature sensor.
MATRIX
35
00
The DencoHappel MATRIX control
electronics are built into the electric
switch cabinet.
For each connectable component
an individual table indicates possi-
bilities of connecting electric equip-
ment to the supplied controller
hardware.
Fig. 6-9:
Overview controller type
NOTICE!
The installation site of the room temperature sensor is crucial for the precise
control of room temperature. Therefore avoid mounting the sensor in the follow-
ing locations (refer to Fig. 6-10):
–
Not next to doors, windows, hatches etc., as intense movement of air can
cause incorrect measurements and affect control operation.
–
Hot or cold walls (e.g. chimney, outside wall), as wall temperature can cause
incorrect measurements and affect control operation.
–
Do not place behind blinds and net curtains, as the insulating layers of air
can cause incorrect measurements.
–
In the direct vicinity of the units' discharge grille as discharge temperature
can cause incorrect measurements.
If no optimum mounting location for an IP20 control panel is available, or if a
IP54 control panel is supplied, a separate room temperature sensor or return-
air sensor must be fitted.
This automatically disables all temperature sensors fitted in the control panel.