![Denco HyCassette-Geko Скачать руководство пользователя страница 84](http://html1.mh-extra.com/html/denco/hycassette-geko/hycassette-geko_operation-manual_2480034084.webp)
Electrical Connection
HyCassette-Geko
81
PR-2015-0159-GB • Subject to modifications • R1-11/2015
3-point modulating actuators (valve code VR..., VC...,
V5...)
Pos. 1:
Cooling valve
Pos. 2:
Heating valve
Fig. 6-22: Valve connection 4-pipe system, 3-point modu-
lating actuators
Unit
with
MATRIX
3500
230 V AC /
50Hz
MATRIX
3500
✓
Valve
Kl. 102
Kl. 103
Kl. 104
Kl. 105
Kl. N
2-way
brown
black
brown
black
blue
3-way
black
brown
black
brown
blue
2-point modulating actuators (cooling) - 3-point
modulating actuators (heating)
(valve code V1...)
Pos. 1:
Cooling valve
Pos. 2:
Heating valve
Fig. 6-23: Valve connection 4-pipe system, 2- and 3-point
modulating actuators
Unit
with
MATRIX
3500
230 V AC /
50Hz
MATRIX
3500
✓
Valve
Kl. 103
Kl. 104
Kl. 105
Kl. N
2-way
brown
brown
black
blue
3-way
brown
black
brown
blue
3-point modulating actuators (cooling) - 2-point
modulating actuators (heating)
(valve code V2...)
Pos. 1:
Cooling valve
Pos. 2:
Heating valve (not included for units with electrical
heating)
Fig. 6-24: Valve connection 4-pipe system, 3- and 2-point
modulating actuators
Unit
with
MATRIX
3500
230 V AC /
50Hz
MATRIX
3500
✓
Valve
Kl. 103
Kl. 104
Kl. 105
Kl. N
2-way
brown
black
brown
blue
3-way
black
brown
brown
blue