FUNCTIONS
47
7
7.7.7 Partial muting
It’s possible to configure the type of muting: total or partial. Partial muting can be useful in
those applications in which the user wants to limit the muting function effects to selected
zones only.
In ACM Configuration the user can select a maximum of 5 muting zones, each defined with
the following parameters:
-
Position:
first beam of muting zone (starting from user display cap)
-
Dimension:
number of beams of muting zone
ACM Configuration: Partial Muting Selection
Check “Partial Muting” to enable function.
Click “+” button to add a new muting zone, X to remove a selected one
Choose correct parameters for selected zone. Both Dimension and Position are set in beams unit,
equivalent measures in mm are exposed by GUI.