SG4 EXTENDED INSTRUCTION MANUAL
38
7
7.5 EDM
SELECTION
This function lets the user to select or exclude the monitoring of the external switching
devices.
BCM Configuration: EDM Selection
Enabled
Led 4 ON Yellow
Disabled
Led 4 OFF
ACM Configuration: EDM Selection
To increase safety level, when EDM is set OFF, at start-up ESPE checks if EDM input is
floating.
7.6 REDUCTION
RANGE
This function allows the user to select the maximum operating distance at which the curtains
can be mounted.
When Long Range is selected on RX, if TX is configured as
Long Range, the maximum operating distance is 20m (30mm resolution) and 7m (14mm
resolution); if TX is configured as Short Range the maximum operating distance is 12m
(30mm resolution) and 4m (14mm resolution).
When Short Range is selected on RX, if TX is configured as Long Range, the maximum
operating distance is 6m (30mm resolution) and 2m (14mm resolution); if TX is configured as
Short Range the maximum operating distance is 4m (30mm resolution) and 1m (14mm
resolution).
Please refer to the table on the next page.
The user can select this function for RX side through ACM and for TX side through BCM.
Fig. 38 – Reduction Range
Содержание SG4-14-030-OO-P
Страница 1: ...SG4 EXTENDED Instruction Manual ...
Страница 3: ......
Страница 86: ...SG4 EXTENDED INSTRUCTION MANUAL 78 14 14OUTFIT Angled fixing bracket with threaded pins metallic insert ...
Страница 93: ...ACCESSORIES 85 15 Fixing kit MODEL DESCRIPTION CODE ST DM Kit STAND ALONE 95ASE1940 ...
Страница 105: ...ACCESSORIES 97 15 SG4 EXTENDED BRACCI ATTIVO PASSIVO L SG4 EXTENDED BRACCI ATTIVO PASSIVO T ...
Страница 108: ...www datalogic com ...