5-68 Pulse Output Max Freq #X30/6
Select the maximum frequency on terminal X30/6 referring to the
output variable in
5-66 Terminal X30/6 Pulse Output Variable
. This
parameter cannot be adjusted while the motor is running.
This parameter is active when option module MCB 101 is mounted
in the frequency converter.
Range:
Function:
Application
dependent
*
[0 - 32000 Hz]
3.7.8 5-9* Bus Controlled
This parameter group selects digital and relay outputs via a
fieldbus setting.
5-90 Digital & Relay Bus Control
Range:
Function:
0
*
[0 - 2147483647 ] This parameter holds the state of the
digital outputs and relays that is
controlled by bus.
A logical '1' indicates that the output is
high or active.
A logical '0' indicates that the output is
low or inactive.
Bit 0
CC Digital Output Terminal 27
Bit 1
CC Digital Output Terminal 29
Bit 2
GPIO Digital Output Terminal X 30/6
Bit 3
GPIO Digital Output Terminal X 30/7
Bit 4
CC Relay 1 output terminal
Bit 5
CC Relay 2 output terminal
Bit 6
Option B Relay 1 output terminal
Bit 7
Option B Relay 2 output terminal
Bit 8
Option B Relay 3 output terminal
Bit 9-15
Reserved for future terminals
Bit 16
Option C Relay 1 output terminal
Bit 17
Option C Relay 2 output terminal
Bit 18
Option C Relay 3 output terminal
Bit 19
Option C Relay 4 output terminal
Bit 20
Option C Relay 5 output terminal
Bit 21
Option C Relay 6 output terminal
Bit 22
Option C Relay 7 output terminal
Bit 23
Option C Relay 8 output terminal
Bit 24-31
Reserved for future terminals
5-93 Pulse Out #27 Bus Control
Range:
Function:
0.00 %
*
[0.00 - 100.00 %] Contains the frequency to apply to
the digital output terminal 27, when it
is configured as [Bus Controlled].
5-94 Pulse Out #27 Timeout Preset
Range:
Function:
0.00 %
*
[0.00 - 100.00
%]
Contains the frequency to apply to the
digital output terminal 27, when it is
configured as [Bus Controlled Timeout]
and timeout is detected.
5-95 Pulse Out #29 Bus Control
Range:
Function:
0.00 %
*
[0.00 - 100.00 %] Contains the frequency to apply to
the digital output terminal 29, when it
is configured as [Bus Controlled].
5-96 Pulse Out #29 Timeout Preset
Range:
Function:
0.00 %
*
[0.00 - 100.00
%]
Contains the frequency to apply to the
digital output terminal 29, when it is
configured as [Bus Controlled Timeout]
and timeout is detected
5-97 Pulse Out #X30/6 Bus Control
Range:
Function:
0.00 %
*
[0.00 - 100.00 %] Contains the frequency to apply to
the digital output terminal 27, when
it is configured as [Bus Controlled.
5-98 Pulse Out #X30/6 Timeout Preset
Range:
Function:
0.00 %
*
[0.00 - 100.00
%]
Contains the frequency to apply to the
digital output terminal 6, when it is
configured as [Bus Controlled Timeout]
and time-out is detected.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
67