0-11 Programming Set-up
Option:
Function:
Select the set-up to be edited (i.e.
programmed) during operation; either the
active set-up or one of the inactive set-ups. The
set-up number being edited is displayed in the
LCP in (brackets).
[0]
Factory
setup
cannot be edited but it is useful as a data
source to return the other set-ups to a known
state.
[1]
Set-up 1
Set-up 1
[1] to
Set-up 4
[4] can be edited freely
during operation, independently of the active
set-up.
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
*
Active Set-
up
(i.e. the set-up in which the frequency
converter is operating) can also be edited
during operation. Editing parameters in the
chosen setup would normally be done from the
LCP but it is also possible from any of the serial
communication ports.
0-12 This Set-up Linked to
Option:
Function:
This parameter only needs to be programmed if
changing set-ups is required whilst the motor is
running. It ensures that parameters which are
"not changeable during operation" have the
same setting in all relevant set-ups.
To enable conflict-free changes from one set-up
to another whilst the frequency converter is
running, link set-ups containing parameters
which are not changeable during operation. The
link will ensure synchronising of the ‘not
changeable during operation’ parameter values
when moving from one set-up to another during
operation. ‘Not changeable during operation’
parameters can be identified by the label FALSE
in the parameter lists in the section
Parameter
Lists
.
The
feature is used
when Multi set-up in
is
selected. Multi set-up can be used to move from
one set-up to another during operation (i.e. while
the motor is running).
Example:
Use Multi set-up to shift from Set-up 1 to Set-up
2 whilst the motor is running. Programme
parameters in Set-up 1 first, then ensure that Set-
up 1 and Set-up 2 are synchronised (or ‘linked’).
Synchronisation can be performed in two ways:
1. Change the edit set-up to
Set-up 2
[2] in
and set
0-12 This Set-up Linked to
Option:
Function:
to
Set-up 1
[1]. This will start the linking
(synchronising) process.
130BP075.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[1]
Setup 1
OR
2. While still in Set-up 1, using
copy Set-up 1 to Set-up 2. Then set
to
Set-up 2
[2]. This will start the
linking process.
130BP076.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[2]
Setup 2
After the link is complete,
will read {1,2} to indicate that all ‘not
changeable during operation’ parameters are
now the same in Set-up 1 and Set-up 2. If there
are changes to a ‘not changeable during
operation’ parameter, e.g.
, in Set-up 2, they will also be changed
automatically in Set-up 1. A switch between Set-
up 1 and Set-up 2 during operation is now
possible.
[0]
*
Not linked
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
Parameter Description
VLT
®
HVAC Drive Programming Guide
28
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
3
3