26-60 Terminal X42/11 Output
Option:
Function:
[105] Torque 0-Tnom
: 0 - Motor rated torque, (0-20 mA)
[106] Power 0-Pnom
: 0 - Motor rated power, (0-20 mA)
[107] Speed 0-HighLim : 0 - Speed High Limit (
and
), (0-20 mA)
[113] Ext. Closed Loop
1
: 0 - 100%, (0-20 mA)
[114] Ext. Closed Loop
2
: 0 - 100%, (0-20 mA)
[115] Ext. Closed Loop
3
: 0 - 100%, (0-20 mA)
[139] Bus ctrl.
: 0 - 100%, (0-20 mA)
[141] Bus ctrl t.o.
: 0 - 100%, (0-20 mA)
26-61 Terminal X42/11 Min. Scale
Range:
Function:
0.00 %
*
[0.00 -
200.00 %]
Scale the minimum output of the selected
analog signal at terminal X42/11, as a
percentage of the maximum signal level. E.g.
if a 0 V is desired at 25% of the maximum
output value. Then programme 25%. Scaling
values up to 100% can never be higher than
the corresponding setting in
.
See principle graph for
6-51 Terminal 42 Output Min Scale
26-62 Terminal X42/11 Max. Scale
Range:
Function:
100.00
%
*
[0.00 -
200.00
%]
Scale the maximum output of the selected analog
signal at terminal X42/9. Set the value to the
maximum value of the voltage signal output.
Scale the output to give a voltage lower than 10V
at full scale; or 10V at an output below 100% of
the maximum signal value. If 10V is the desired
output current at a value between 0-100% of the
full-scale output, programme the percentage
value in the parameter, i.e. 50% = 10V. If a voltage
between 0 and 10V is desired at maximum
output, calculate the percentage as follows:
(
10
V
desired maximum voltage
)
x100 %
i.e.
5
V : 10V
5
V x100 % = 200 %
See principle graph for
6-52 Terminal 42 Output Max Scale
26-63 Terminal X42/11 Bus Control
Range:
Function:
0.00 %
*
[0.00 - 100.00 %] Holds the level of terminal X42/11 if
controlled by bus.
26-64 Terminal X42/11 Timeout Preset
Range:
Function:
0.00 %
*
[0.00 - 100.00
%]
Holds the preset level of terminal
X42/11.
In case a bus time-out and a time-out
function are selected, the output will
preset to this level.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
183
3
3