NOTE
For choices [32] - [43], see also parameter group 5-3*,
Digital
Outputs
and 5-4*,
Relays
.
23-02 OFF Time
Array [10]
Range:
Function:
Size related
*
[0 - 0 ]
23-03 OFF Action
Array [10]
Option:
Function:
Select the action during OFF Time.
See
for
descriptions of the options.
[0]
*
Disabled
[1]
No action
[2]
Select set-up 1
[3]
Select set-up 2
[4]
Select set-up 3
[5]
Select set-up 4
[10] Select preset ref 0
[11] Select preset ref 1
[12] Select preset ref 2
[13] Select preset ref 3
[14] Select preset ref 4
[15] Select preset ref 5
[16] Select preset ref 6
[17] Select preset ref 7
[18] Select ramp 1
[19] Select ramp 2
[22] Run
[23] Run reverse
[24] Stop
[26] DC Brake
[27] Coast
[32] Set digital out A low
[33] Set digital out B low
[34] Set digital out C low
[35] Set digital out D low
[36] Set digital out E low
[37] Set digital out F low
[38] Set digital out A high
[39] Set digital out B high
[40] Set digital out C high
[41] Set digital out D high
[42] Set digital out E high
[43] Set digital out F high
[60] Reset Counter A
[61] Reset Counter B
[80] Sleep Mode
23-04 Occurrence
Array [10]
Option:
Function:
Select which day(s) the Timed Action
applies to. Specify working/non-working
days in
and
.
[0]
*
All days
[1]
Working days
[2]
Non-working days
[3]
Monday
[4]
Tuesday
[5]
Wednesday
[6]
Thursday
[7]
Friday
[8]
Saturday
[9]
Sunday
23-08 Timed Actions Mode
Used to enable and disable automatic timed actions.
Option:
Function:
[0]
*
Timed Actions Auto
Enable timed actions.
[1]
Timed Actions Disabled Disable timed actions, normal
operation according to control
commands.
[2]
Constant On Actions
Disable timed actions. Constant On
Actions activated.
[3]
Constant Off Actions
Disable timed actions. Constant Off
Actions activated.
23-09 Timed Actions Reactivation
Option:
Function:
[0]
Disabled After an update of time/condition U(power cycling,
setting date and time, change of summertime,
change of Hand Auto mode, change of Constant
ON and OFF, set-up change) all activated ON
actions will be overridden to OFF actions until
passing the next time for an ON action. Any OFF
actions will remain unchanged.
[1]
*
Enabled After an update of time/condition On and OFF
actions are immediately set to the actual time
programming of ON and OFF actions.
To see an example of a reactivation test, see
.
Parameter Description
VLT
®
HVAC Drive Programming Guide
154
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
3
3