13-02 Stop Event
Option:
Function:
[48]
Down Key
This event is TRUE if the Down key on
the LCP is pressed.
[50]
Comparator 4
Use the result of comparator 4 in the
logic rule.
[51]
Comparator 5
Use the result of comparator 5 in the
logic rule.
[60]
Logic rule 4
Use the result of logic rule 4 in the
logic rule.
[61]
Logic rule 5
Use the result of logic rule 5 in the
logic rule.
[70]
SL Time-out 3
Use the result of timer 3 in the logic
rule.
[71]
SL Time-out 4
Use the result of timer 4 in the logic
rule.
[72]
SL Time-out 5
Use the result of timer 5 in the logic
rule.
[73]
SL Time-out 6
Use the result of timer 6 in the logic
rule.
[74]
SL Time-out 7
Use the result of timer 7 in the logic
rule.
[76]
Digital Input x30 2
[77]
Digital Input x30 3
[78]
Digital Input x30 4
[80]
No Flow
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
[90]
ECB Drive Mode
[91]
ECB Bypass Mode
[92]
ECB Test Mode
[100] Fire Mode
13-03 Reset SLC
Option:
Function:
[0]
*
Do not reset SLC Retains programmed settings in all group
13 parameters (13-*).
[1]
Reset SLC
Resets all group 13 parameters (13-*) to
default settings.
3.13.3 13-1* Comparators
Comparators are used for comparing continuous variables
(i.e. output frequency, output current, analog input etc.) to
fixed preset values.
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
130BB672.10
In addition, there are digital values that will be compared to
fixed time values. See explanation in
. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All
parameters in this parameter group are array parameters
with index 0 to 5. Select index 0 to programme Comparator
0, select index 1 to programme Comparator 1, and so on.
13-10 Comparator Operand
Array [4]
Option:
Function:
Select the variable to be monitored
by the comparator.
[0]
*
DISABLED
[1]
Reference
[2]
Feedback
[3]
Motor speed
[4]
Motor current
[5]
Motor torque
[6]
Motor power
[7]
Motor voltage
[8]
DC-link voltage
[9]
Motor thermal
[10]
Drive thermal
[11]
Heat sink temp.
[12]
Analog input AI53
[13]
Analog input AI54
[14]
Analog input AIFB10
[15]
Analog input AIS24V
[17]
Analog input AICCT
[18]
Pulse input FI29
[19]
Pulse input FI33
[20]
Alarm number
[21]
Warning number
[22]
Analog input x30 11
[23]
Analog input x30 12
[30]
Counter A
[31]
Counter B
[40]
Analog input x42/1
[41]
Analog input x42/3
Parameter Description
VLT
®
HVAC Drive Programming Guide
94