for Output Frequency and Motor Speed.
The size of each interval can be adjusted individually, but will
default be 10% for each. Power and Current can exceed
rated value, but those registrations will be included in
90%-100% (MAX) counter.
Relative value
operating variable
Counter 1: +1
Counter 0: +5
Counter 2: +0
Counter 3: +1
Counter 4: +0
Counter 5: +11
Counter 6: +1
Counter 7: +2
Counter 8: +6
Counter 9: +0
130BA281.10
80
70
50
60
30
40
10
20
%
90
100
Once a second, the value of the operating variable selected
is registered. If a value has been registered to equal 13%, the
counter “10% - <20%” will be updated with the value “1”. If
the value stays at 13% for 10s, then “10” will be added to the
counter value.
The contents of counters can be displayed as bars on LCP.
Select
Quick Menu
>
Loggings
:
Trending Continued Bin /
Trending Timed Bin / Trending Comparison
.
NOTE
The counters starts counting whenever the frequency
converter is powered-up. Power cycle shortly after a reset
will zero the counters. EEProm data are updated once per
hour.
23-60 Trend Variable
Option:
Function:
Select the desired operating variable to be
monitored for Trending.
[0]
*
Power [kW]
Power yielded to the motor. Reference for the
relative value is the rated motor power
programmed in
or
. Actual value can be
read in
or
[1]
Current [A]
Output current to the motor. Reference for the
relative value is the rated motor current
programmed in
. Actual
value can be read in
.
[2]
Frequency
[Hz]
Output frequency to the motor. Reference for
the relative value is the maximum output
frequency programmed in
. Actual value can be read in
.
[3]
Motor Speed
[RPM]
Speed of the motor. Reference for relative
value is the maximum motor speed
23-60 Trend Variable
Option:
Function:
programmed in
23-61 Continuous Bin Data
Range:
Function:
0
*
[0 -
4294967295 ]
Array with 10 elements ([0]-[9] below
parameter number in display). Press OK and
step between elements by means of
▲
and
▼
buttons on the LCP.
10 counters with the frequency of occurrence
for the operating variable monitored, sorted
according to the following intervals:
Counter [0]: 0% - <10%
Counter [1]: 10% - <20%
Counter [2]. 20% - <30%
Counter [3]: 30% - <40%
Counter [4]: 40% - <50%
Counter [5]: 50% - <60%
Counter [6]. 60% - <70%
Counter [7]: 70% - <80%
Counter [8]. 80% - <90%
Counter [9]: 90% - <100% or Max
The above minimum limits for the intervals
are the default limits. These can be changed
in
.
Starts to count when the frequency converter
is powered up for the first time. All counters
can be reset to 0 in
.
23-62 Timed Bin Data
Range:
Function:
0
*
[0 -
4294967295 ]
Array with 10 elements ([0]-[9] below
parameter number in display). Press OK and
step between elements by means of
▲
and
▼
buttons on the LCP.
10 counters with the frequency of occurrence
for the operating data monitored sorted
according to the intervals as for
.
Starts to count at the date/time programmed
in
, and stops at the
time/date programmed in
. All counters can be reset to 0 in
.
23-63 Timed Period Start
Range:
Function:
Size related
*
[0 - 0 ]
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
159
3
3