The following control signals will still be active when [Hand
on] is activated:
•
[Hand on] - [Off] - [Auto on]
•
Reset
•
Coasting stop inverse
•
Reversing
•
Set-up select lsb - Set-up select msb
•
Stop command from serial communication
•
Quick stop
•
DC brake
[Off] stops the connected motor. The key can be selected as
Enable
[1] or
Disable
[0] via
.
If no external stop function is selected and the [Off] key is
inactive the motor can be stopped by disconnecting the
mains supply.
[Auto on] enables the frequency converter to be controlled
via the control terminals and/or serial communication. When
a start signal is applied on the control terminals and/or the
bus, the frequency converter will start. The key can be
selected as
Enable
[1] or
Disable
[0] via
.
NOTE
An active HAND-OFF-AUTO signal via the digital inputs has
higher priority than the control keys [Hand on] [Auto on].
[Reset] is used for resetting the frequency converter after an
alarm (trip). It can be selected as
Enable
[1] or
Disable
[0] via
2.1.3 Quick Transfer of Parameter Settings
between Multiple Frequency
Converters
Once the set-up of a frequency converter is complete, we
recommend that you store the data in the LCP or on a PC via
MCT 10 Set-up Software Tool.
Auto
on
Reset
Hand
on
Off
Status
Quick
Menu
Main
Menu
Alarm
Log
Back
Canc
el
In
fo
OK
On
Alarm
Warn.
130BA027.10
Data storage in LCP:
1.
Go to
2.
Press the [OK] key
3.
Select “All to LCP”
4.
Press the [OK] key
All parameter settings are now stored in the LCP indicated by
the progress bar. When 100% is reached, press [OK].
NOTE
Stop the motor before performing this operation.
You can now connect the LCP to another frequency
converter and copy the parameter settings to this frequency
converter as well.
Data transfer from LCP to frequency converter:
1.
Go to
2.
Press the [OK] key
3.
Select “All from LCP”
4.
Press the [OK] key
The parameter settings stored in the LCP are now transferred
to the frequency converter indicated by the progress bar.
When 100% is reached, press [OK].
NOTE
Stop the motor before performing this operation.
How to Programme
VLT
®
HVAC Drive Programming Guide
16
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark