3.7.3 5-1* Digital Inputs continued
All = Terminals 18, 19, 27, 29, 32, 33, X30/2, X30/3, X30/4.
X30/ are the terminals on MCB 101.
Functions dedicated to only one digital input are stated in
the associated parameter.
All digital inputs can be programmed to these functions:
[0]
No operation
No reaction to signals transmitted to
terminal.
[1]
Reset
Resets frequency converter after a TRIP/
ALARM. Not all alarms can be reset.
[2]
Coast inverse
Leaves motor in free mode. Logic ‘0’ =>
coasting stop.
(Default Digital input 27): Coasting stop,
inverted input (NC).
[3]
Coast and
reset inverse
Reset and coasting stop Inverted input (NC).
Leaves motor in free mode and resets the
frequency converter. Logic ‘0’ => coasting
stop and reset.
[5]
DC-brake
inverse
Inverted input for DC braking (NC).
Stops motor by energizing it with a DC
current for a certain time period. See
to
. The function is only active when the
value in
is different
from 0. Logic ’0’ => DC braking.
[6]
Stop inverse
Stop Inverted function. Generates a stop
function when the selected terminal goes
from logical level ‘1’ to ‘0’. The stop is
performed according to the selected ramp
time (
,
,
3-62 Ramp 3
Ramp down Time
,
3-72 Ramp 4 Ramp Down
Time
).
NOTE
When the frequency converter is at the
torque limit and has received a stop
command, it may not stop by itself. To
ensure that the frequency converter
stops, configure a digital output to
Torque limit & stop
[27] and connect this
digital output to a digital input that is
configured as coast.
[7]
External
Interlock
Same function as Coasting stop, inverse, but
External Interlock generates the alarm
message ’external fault’ on the display when
the terminal which is programmed for Coast
Inverse is logic ‘0’. The alarm message will
also be active via digital outputs and relay
outputs, if programmed for External
Interlock. The alarm can be reset using a
digital input or the [RESET] key if the cause
for the External Interlock has been removed.
A delay can be programmed in
, External Interlock Time. After
applying a signal to the input, the reaction
described above will be delayed with the
time set in
22-00 External Interlock Delay
.
[8]
Start
Select start for a start/stop command. Logic
‘1’ = start, logic ‘0’ = stop.
(Default Digital input 18)
[9]
Latched start
Motor starts, if a pulse is applied for min. 2
ms. Motor stops when Stop inverse is
activated
[10] Reversing
Changes direction of motor shaft rotation.
Select Logic ‘1’ to reverse. The reversing
signal only changes the direction of rotation.
It does not activate the start function. Select
both directions in
.
(Default Digital input 19).
[11] Start reversing Used for start/stop and for reversing on the
same wire. Signals on start are not allowed at
the same time.
[14] Jog
Used for activating jog speed. See
.
(Default Digital input 29)
[15] Preset
reference on
Used for shifting between external reference
and preset reference. It is assumed that
External/preset
[1] has been selected in
. Logic '0' = external
reference active; logic '1' = one of the eight
preset references is active.
[16] Preset ref bit 0 Enables a choice between one of the eight
preset references according to the table
below.
[17] Preset ref bit 1 Enables a choice between one of the eight
preset references according to the table
below.
[18] Preset ref bit 2 Enables a choice between one of the eight
preset references according to the table
below.
Preset ref. bit
2
1
0
Preset ref. 0
0
0
0
Preset ref. 1
0
0
1
Preset ref. 2
0
1
0
Preset ref. 3
0
1
1
Preset ref. 4
1
0
0
Preset ref. 5
1
0
1
Preset ref. 6
1
1
0
Preset ref. 7
1
1
1
[19] Freeze ref
Freezes actual reference. The frozen
reference is now the point of enable/
condition for Speed up and Speed down to
be used. If Speed up/down is used, the speed
change always follows ramp 2 (
and
) in the range 0 -
3-03 Maximum
Parameter Description
VLT
®
HVAC Drive Programming Guide
58
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
3
3
Содержание VLT
Страница 1: ...MAKING MODERN LIVING POSSIBLE Programming Guide VLT HVAC Drive...
Страница 230: ...www danfoss com drives MG11CB02 130R0318 MG11CB02 Rev 2010 09 10...
Страница 231: ......