Reference
. (For closed loop see
20-14 Maximum Reference/Feedb.
).
[20] Freeze output
Freezes actual motor frequency (Hz). The
frozen motor frequency is now the point of
enable/condition for Speed up and Speed
down to be used. If Speed up/down is used,
the speed change always follows ramp 2
(
and
) in the range 0 -
NOTE
When Freeze output is active, the
frequency converter cannot be stopped
via a low ‘start [13]’ signal. Stop the
frequency converter via a terminal
programmed for Coasting inverse [2] or
Coast and reset, inverse [3].
[21] Speed up
For digital control of the up/down speed is
desired (motor potentiometer). Activate this
function by selecting either Freeze reference
or Freeze output. When Speed up is
activated for less than 400 msec. the
resulting reference will be increased by 0.1
%. If Speed up is activated for more than 400
msec. the resulting reference will ramp
according to Ramp 1 in
.
[22] Speed down
Same as Speed up [21].
[23] Set-up select
bit 0
Selects one of the four set-ups. Set par. 0-10
to Multi Set-up.
[24] Set-up select
bit 1
Same as Set-up select bit 0 [23].
(Default Digital input 32)
[32] Pulse input
Select Pulse input when using a pulse
sequence as either reference or feedback.
Scaling is done in parameter group 5-5*.
[34] Ramp bit 0
Select which ramp to use. Logic “0” will select
ramp 1 while logic “1” will select ramp 2.
[36] Mains failure
inverse
Select to activate function selected in
. Mains failure is active in
the Logic “0” situation.
[37] Fire mode
A signal applied will put the frequency
converter into Fire Mode and all other
commands will be disregarded. See 24-0*
Fire Mode
.
[52] Run Permissive The input terminal, for which the Run
permissive has been programmed must be
logic “1” before a start command can be
accepted. Run permissive has a logic ‘AND’
function related to the terminal which is
programmed for
START
[8],
Jog
[14] or
Freeze
Output
[20], which means that in order to
start running the motor, both conditions
must be fulfilled. If Run Permissive is
programmed on multiple terminals, Run
permissive needs only be logic ‘1’ on one of
the terminals for the function to be carried
out. The digital output signal for Run
Request (
Start
[8],
Jog
[14] or
Freeze output
[20]) programmed in par. 5-3*, or par. 5-4*,
will not be affected by Run Permissive.
NOTE
If no Run Permissive signal is applied
but either Run, Jog or Freeze commands
is activated, the status line in the display
will show either Run Requested, Jog
Requested or Freeze Requested.
[53] Hand start
A signal applied will put the frequency
converter into Hand mode as if button
Hand
On
on the LCP has been pressed and a
normal stop command will be overridden. If
disconnecting the signal, the motor will stop.
To make any other start commands valid,
another digital input must be assign to
Auto
Start
and a signal applied to this. The
Hand
On
and
Auto On
buttons on the LCP has no
impact. The
Off
button on the LCP will
override
Hand Start
and
Auto Start
. Press
either the
Hand On
or
Auto On
button to
make
Hand Start
and
Auto Start
active again.
If no signal on neither
Hand Start
nor
Auto
Start
, the motor will stop regardless of any
normal Start command applied. If signal
applied to both
Hand Start
and
Auto Start
,
the function will be
Auto Start
. If pressing the
Off
button on the LCP the motor will stop
regardless of signals on
Hand Start
and
Auto
Start
.
[54] Auto start
A signal applied will put the frequency
converter into Auto mode as if the LCP
button
Auto On
has been pressed. See also
Hand Start
[53]
[55] DigiPot
Increase
Uses the input as an INCREASE signal to the
Digital Potentiometer function described in
parameter group 3-9*
[56] DigiPot
Decrease
Uses the input as a DECREASE signal to the
Digital Potentiometer function described in
parameter group 3-9*
[57] DigiPot Clear
Uses the input to CLEAR the Digital Potenti-
ometer reference described in parameter
group 3-9*
[60] Counter A (up) (Terminal 29 or 33 only) Input for increment
counting in the SLC counter.
[61] Counter A
(down)
(Terminal 29 or 33 only) Input for decrement
counting in the SLC counter.
[62] Reset Counter
A
Input for reset of counter A.
[63] Counter B (up) (Terminal 29 and 33 only) Input for
increment counting in the SLC counter.
[64] Counter B
(down)
(Terminal 29 and 33 only) Input for
decrement counting in the SLC counter.
[65] Reset Counter
B
Input for reset of counter B.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®