Timed Action
ON: RUN
OFF: STOP
Power
Cycle
P23-09:
Disabled
Power
Cycle
P23-09:
Disabled
P23-09:
Disable
Enable
Power
Cycle
P23-09:
Enabled
Status
RUNNING
STOPPED
130BB808.10
Illustration 3.6 Reactivation Test Diagram
3.21.2 23-1* Maintenance
Wear and tear calls for periodic inspection and service of
elements in the application, e.g. motor bearings, feedback
sensors and seals or filters. With Preventive Maintenance the
service intervals may be programmed into the frequency
converter. The frequency converter will give a message when
maintenance is required. 20 Preventive Maintenance Events
can be programmed into the frequency converter. For each
Event the following must be specified:
•
Maintenance item (e.g. “Motor Bearings”)
•
Maintenance action (e.g. “Replace”)
•
Maintenance Time Base (e.g. “Running Hours” or a
specific date and time)
•
Maintenance Time Interval or the date and time of
next maintenance
NOTE
To disable a Preventive Maintenance Event the associated
must be set to
Disabled
[0].
Preventive Maintenance can be programmed from the LCP,
but use of the PC-based VLT Motion Control Tool MCT10 is
recommended.
+
-
+
-
-
-
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
+
130BA492.10
Untitled - MCT 10 SET - up Software
File
Edit
View Insert Communication
Tools Options Help
ID
Name
Setup 1
Setup 2
Setup 3
Setup 4
2310.0
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.1
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.2
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.3
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.4
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.5
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.6
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.7
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.8
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.9
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.10
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.11
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.12
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.13
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.14
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.15
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.16
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.17
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.18
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2310.19
Maintenance Item
Motor bearings
Motor bearings
Motor bearings
Motor bearings
2311.0
Maintenance Action
Lubricate
Lubricate
Lubricates
Lubricate
2311.2
Maintenance Action
Lubricate
Lubricate
Lubricates
Lubricate
2311.3
Maintenance Action
Lubricate
Lubricate
Lubricates
Lubricate
2311.4
Maintenance Action
Lubricate
Lubricate
Lubricates
Lubricate
2311.5
Maintenance Action
Lubricate
Lubricate
Lubricates
Lubricate
2311.6
Maintenance Action
Lubricate
Lubricate
Lubricates
Lubricate
Network
Project
VLT AQUA DRIVE
All Parameters
Operation/Display
Load/Motor
Brakes
Reference / Ramps
Limits / Warnings
Digital In/Out
Analog In/Out
Comm. andOptions
Smart logic
Special Functions
Drive Information
Data Readouts
Info & Readouts
Drive Closed Loop
Ext. Closed Loop
Application Functions
Time-based Functions
Timed Actions
Maintenance
Maintenance Reset
Energy Log
Trending
Payback Counter
Cascade Controller
Water Application Functions
Cascade Controller
The LCP indicates (with a wrench-icon and an “M”) when it is
time for a Preventive Maintenance Action, and can be
programmed to be indicated on a digital output in
parameter group 5-3*. The Preventive Maintenance Status
may be read in
. A Preventive
Maintenance indication can be reset from a digital input, the
FC bus or manually from the LCP through
A Maintenance Log with the latest 10 loggings can be read
from parameter group 18-0* and via the Alarm log button on
the LCP after selecting Maintenance Log.
Parameter Description
VLT
®
HVAC Drive Programming Guide
MG.11.CB.02 - VLT
®
is a registered Danfoss trademark
155
3
3