3 How to Install
3.1 Connecting the Bus Line
Terminate the bus line at both ends of each segment. A
mismatch of impedance may result in reflections on the
line resulting in corrupt data transmission.
The Profibus Option Card contains a suitable termination.
To activate the termination, turn on
Switch 1
on the
Profibus converter option. By default, the switch is turned
off.
NOTICE
Notice that pin numbers are colour
coded on the Profibus connector.
Unlike the VLT
®
5000, the FC 302 Profibus connectors are
colour-coded to avoid swapping the bus wires.
Illustration 3.1 Connecting Bus Wires to VLT PROFIBUS
Converter MCA 114
Profibus B
62 = RxD/TxD
Positive, red cable
Profibus A
63 = RxD/TxD
Negative, green cable
Table 3.1 Correct Colour-Coding
3.2 How to Install Option in Frequency
Converter
130B
T318.11
Illustration 3.2 Installing Fieldbus Option
Illustration 3.3 Cable Holders
1.
Remove the LCP from the FC 302.
2.
Remove the frame below the local control panel.
How to Install
VLT
®
AutomationDrive FC 302 PROFIBUS Converter Operating Instructions