5.6 VLT
®
5000 Parameter Group 5
VLT 5000 series
FC 302 series
Parameter
500 Address
8-31 Address
Range
0 - 126
0 - 126
Table 5.183 Conversion of Parameter 500
VLT 5000 series
FC 302 series
Parameter
501 Baud rate
8-32 FC Port Baud Rate
Options
[0] 300
Not supported
[1] 600
Not supported
[2] 1200
Not supported
[3] 2400
[0] 2400
[4] 4800
[1] 4800
[5] 9600
[2] 9600
Table 5.184 Conversion of Parameter 501
VLT 5000 series
FC 302 series
Parameter
502 Coasting
8-50 Coasting Select
Parameter
503 Quick - Stop
8-51 Quick Stop Select
Parameter
504 DC brake
8-52 DC Brake Select
Parameter
505 Start
8-53 Start Select
Parameter
506 Reversing
8-54 Reversing Select
Parameter
507 Setup select
8-55 Set-up Select
Parameter
508 Preset reference
select
8-56 Preset Reference
Select
Parameter
type
Unsigned 8 (5)
Unsigned 8 (5)
Options
[0] Digital input
[0] Digital input
[1] Bus
[1] Bus
[2] Logic AND
[2] Logic AND
[3] Logic OR
[3] Logic OR
Table 5.185 Conversion of Parameter 502 - 508
VLT 5000 series
FC 302 series
Parameter
509 Bus Jog 1
8-90 Bus Jog 1 Speed
Range
0.0 – par. 202
0.0 – par. 4-13
Table 5.186 Conversion of Parameter 509
VLT 5000 series
FC 302 series
Parameter
510 Bus Jog 2
8-91 Bus Jog 2 Speed
Range
0.0 – par. 202
0.0 – par. 4-13
Table 5.187 Conversion of Parameter 510
VLT 5000 series
FC 302 series
Parameter 512 Telegram Profile
8-10 Control Word Profile
Range
[0] Fieldbus profile
[1] ProfiDrive profile
[1] FC profile
[0] FC profile
Table 5.188 Conversion of Parameter 512
VLT 5000 series
FC 302 series
Parameter
513 Bus time interval
Not Converted
Table 5.189 Conversion of Parameter 513
VLT 5000 series
FC 302 series
Parameter
514 Bus time interval function
Not Converted
Table 5.190 Conversion of Parameter 514
VLT 5000 series
FC 302 series
Parameter
515 Reference %
16-02 Reference %
Table 5.191 Conversion of Parameter 515
VLT 5000 series
FC 302 series
Parameter
516 Reference Unit
16-01 Reference [Unit]
Table 5.192 Conversion of Parameter 516
VLT 5000 series
FC 302 series
Parameter
517 Feedback
16-52 Feedback[Unit]
Table 5.193 Conversion of Parameter 517
VLT 5000 series
FC 302 series
Parameter
518 Frequency
16-13 Frequency
Table 5.194 Conversion of Parameter 518
VLT 5000 series
FC 302 series
Parameter
519 Frequency x scaling
Not converted
Table 5.195 Conversion of Parameter 519
VLT 5000 series
FC 302 series
Parameter
520 Current
16-14 Motor current
Table 5.196 Conversion of Parameter 520
VLT 5000 series FC 302 series
Parameter 521 Torque
16-22 Torque [%]
16-21 Torque [%] high resolution
Table 5.197 Conversion of Parameter 521
VLT 5000 series
FC 302 series
Parameter
522 Power, kW
16-10 Power [kW]
Table 5.198 Conversion of Parameter 522
VLT 5000 series
FC 302 series
Parameter
523 Power, HP
16-11 Power [hp]
Table 5.199 Conversion of Parameter 523
VLT 5000 series
FC 302 series
Parameter
524 Motor voltage
16-12 Motor Voltage
Table 5.200 Conversion of Parameter 524
VLT 5000 series
FC 302 series
Parameter
525 DC link voltage
16-30 DC Link Voltage
Table 5.201 Conversion of Parameter 525
Parameter Mapping Lists
VLT
®
AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
34