VLT 5000
series
FC 302 series
Parameter 308 Terminal
53, Analogue
Input Voltage
3-15 Reference Resource 1
7-00 Speed PID Feedback Source
1-93 Thermistor Resource
4-20 Torque Limit Factor Source
Options
[0] No
Operation
Par. 3-15 Reference resource 1 set to
[0] No function
[1] Reference
Par. 3-15 Reference resource 1 set to
[1] Analog input 53
[2] Feedback
signal
Par. 3-15 Reference resource 1 set to
[1] Analog input 53
Par. 7-00 Speed PID Feedback
Source set to [6] Analog input 53
[3] Torque
limit
Par. 3-15 Reference resource 1 set to
[1] Analog input 53
Par. 4-20 Torque Limit Factor Source
set to [2] Analog in 53
[4] Thermistor Par. 3-15 Reference resource 1 set to
[0] No function
Par. 1-93 Thermistor Ressource set to
[1] Analog input 53
Table 5.95 Conversion of Parameter 308
VLT 5000 series
FC 302 series
Parameter 309 Terminal 53, min.
scaling
6-10 Terminal 53 Low
Voltage
Range
0 – 10.0 Volt
-10.00 – Par. 6-11
Table 5.96 Conversion of Parameter 309
VLT 5000 series
FC 302 series
Parameter 310 Terminal 53, max.
scaling
6-11 Terminal 53 High
Voltage
Range
0 – 10.0 Volt
Par. 6-10 - 10.00 Volt
Table 5.97 Conversion of Parameter 310
VLT 5000 series
FC 302 series
Parameter
311 Terminal 54,
Analogue Input
Voltage
3-16 Reference
Resource 2
7-00 Speed PID
Feedback Source
4-20 Torque Limit
Factor Source
1-93 Thermistor
Resource
4-21 Speed Limit
Factor Source
Options
[0] No Operation
Par. 3-16 Reference
resource 2 set to [0]
No function
[1] Reference
Par. 3-16 Reference
resource 1 set to [2]
Analog input 53
[2] Torque limit
Par. 4-20 Torque
Limit Factor Source
set to [6] Analog in
54
[3] Thermistor
Par. 1-93 Thermistor
Ressource set to [2]
Analog input 54
[4] Relative
reference
Not supported
[5] Max. torque
frequency
Par. 4-21 Speed
Limit Factor Source
set to [6] Analog in
54
Table 5.98 Conversion of Parameter 311
VLT 5000 series
FC 302 series
Parameter 312 Terminal 54, min.
scaling
6-20 Terminal 54 Low
Voltage
Range
0 – 10.0 Volt
-10.00 – Par. 6-21
Table 5.99 Conversion of Parameter 312
VLT 5000 series
FC 302 series
Parameter 313 Terminal 54, max.
scaling
6-21 Terminal 54 High
Voltage
Range
0 – 10.0 Volt
Par. 6-20 - 10.00 Volt
Table 5.100 Conversion of Parameter 313
Parameter Mapping Lists
VLT
®
AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
MG34N202 - Rev. 2013-10-15
23
5
5