5.4 VLT
®
5000 Parameter Group 3
VLT 5000 series
FC 302 series
Parameter 300 Terminal 16, input
5-16 Terminal X30/2
Digital Input
Options
[0] No function
[0] No function
[1] Reset
[1] Reset
[2] Stop inverse
[6] Stop inverse
[3] Only start clockwise,
on
[12] Enable start forward
[4] Jog
[14] Jog
[5] Preset reference, on
[15] Preset reference, on
[6] Preset reference, lsb
[16] Preset reference bit
0
[7] Freeze reference
[17] Freeze reference
[8] Freeze output
[20] Freeze output
[9] Speed up
[21] Speed up
[10] Choice of setup, lsb
[23] Setup select bit 0
[11] Catch-up
[28] Catch-up
[12] Ramp 2
[34] Ramp bit 0
[13] Mains failure inverted Not supported
[29] Data change lock
Not supported
Comments FC 300 does not have a digital input 16, so this is
linked to
5-16 Terminal X30/2 Digital Input
Table 5.87 Conversion of Parameter 300
VLT 5000 series
FC 302 series
Parameter 301 Terminal 17, input
5-17 Terminal X30/3
Digital Input
Options
[0] No function
[0] No operation
[1] Reset
[1] Reset
[2] Stop inverse
[6] Stop inverse
[3] Only start anticlockwise,
on
[13] Enable start reverse
[4] Jog
[14] Jog
[5] Preset reference, on
[15] Preset reference,
on
[6] Preset reference, msb
[17] Preset reference bit
1
[7] Freeze reference
[19] Freeze reference
[8] Freeze output
[20] Freeze output
[9] Speed down
[22] Speed down
[10] Choice of setup, msb
[24] Setup select bit 1
[11] Slow down
[29] Slow down
[12] Ramp 2
[34] Ramp bit 0
[13] Mains failure inverted
Not supported
[23] Pulse reference
[32] Pulse input
[24] Safety interlock
Not supported
[29] Data change lock
Not supported
Comments FC 300 does not have a digital input 17, so this is
linked to
5-16 Terminal X30/2 Digital Input
Table 5.88 Conversion of Parameter 301
VLT 5000 series
FC 302 series
Parameter 302 Terminal 18, input
5-10 Terminal 18 Digital
Input
Options
[0] No function
[0] No operation
[1] Start
[8] Start
[2] Latched start
[9] Latched start
[3] Only start clockwise,
on
[12] Enable start forward
Table 5.89 Conversion of Parameter 302
VLT 5000 series
FC 302 series
Parameter 303 Terminal 19, input
5-11 Terminal 19 Digital
Input
Options
[0] No function
[0] No operation
[1] Reversing
[10] Reversing
[2] Start reversing
[11] Start reversing
[3] Only start
anticlockwise, on
[13] Enable start reverse
Table 5.90 Conversion of Parameter 303
VLT 5000 series
FC 302 series
Parameter 304 Terminal 27, input
5-12 Terminal 27 Digital
Input
Options
[0] Coasting stop,
inverse
[2] Coast inverse
[1] Reset and Coasting
stop, inv.
[3] Coast and reset inv
[2] Quick-stop, inverse
[4] Quick-stop, inverse
[3] DC-braking, inverse
[5] DC-brake inverse
[4] Stop inverse
[6] Stop inverse
Table 5.91 Conversion of Parameter 304
Parameter Mapping Lists
VLT
®
AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
MG34N202 - Rev. 2013-10-15
21