VLT 5000 series
FC 302 series
Parameter 409 Trip delay torque 14-25 Trip Delay at Torque
Limit
Range
0 – 60 s (60=OFF)
0 – 60 s (60=OFF)
Table 5.137 Conversion of Parameter 409
VLT 5000 series
FC 302 series
Parameter 410 Trip delay inverter 14-26 Trip Delay at Inverter
Fault
Range
0 – 35 s
0 – 35 s
Table 5.138 Conversion of Parameter 410
VLT 5000 series
FC 302 series
Parameter 411 Switching frequency 14-01 Switching Frequency
Range
Unsigned 16 (6)
Unsigned 8 (5)
1.5 – 14 kHz
< 2.3
⇒
2.0 kHz [2]
2.3 > 2.7
⇒
2.5 kHz [3]
2.8 > 3.2
⇒
3.0 kHz [4]
3.3 > 3.7
⇒
3.5 kHz [5]
3.8 > 4.5
⇒
4.0 kHz [6]
4.6 > 5.5
⇒
5.0 kHz [7]
5.6 > 6.5
⇒
6.0 kHz [8]
6.6 > 7.5
⇒
7.0 kHz [9]
7.6 > 9.0
⇒
8.0 kHz [10]
9.1 >
⇒
10.0 kHz [11]
Table 5.139 Conversion of Parameter 411
VLT 5000 series
FC 302 series
Parameter 412 Output frequency dependent
switching frequency
Not converted
Table 5.140 Conversion of Parameter 412
VLT 5000 series
FC 302 series
Parameter 413 Overmodulation
function
14-03 Overmodulation
function
Options
[0] Off
[0] Off
[1] On
[1] On
Table 5.141 Conversion of Parameter 413
VLT 5000 series
FC 302 series
Parameter
414 Minimum feedback
Not converted
Table 5.142 Conversion of Parameter 414
VLT 5000 series
FC 302 series
Parameter
415 Maximum feedback
Not converted
Table 5.143 Conversion of Parameter 415
VLT 5000 series
FC 302 series
Parameter
416 Feedback Unit
3-01 Reference/
feedback Unit
Options
[0] None
[0] None
[1] %
[1] %
[2] PPM
[5] PPM
[3] rpm
[2] RPM
[4] bar
[71] bar
[5] Cycle/min
Not supported
[6] Pulse/s
[12] Pulse/s
[7] Unit s/s
Not supported
[8] Unit s/min
Not supported
[9] Unit s/h
Not supported
[10] °C
[60] °C
[11] Pa
[72] Pa
[12] l/s
[20] l/s
[13] m3/s
[23] m3/s
[14] l/min
[21] l/min
[15] m3/min
[24] m3/min
[16] l/h
[22] l/h
[17] m3/h
[25] m3/h
[18] kg/s
[30] kg/s
[19] kg/min
[31] kg/min
[20] kg/h
[32] kg/h
[21] t/min
[33] t/min
[22] t/h
[34] t/h
[23] m
[45] m
[24] Nm
[4] Nm
[25] m/s
[40] m/s
Table 5.144 Conversion of Parameter 416 part 1
Parameter Mapping Lists
VLT
®
AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
30
MG34N202 - Rev. 2013-10-15