VLT
5000
series
FC 302 series
Parameter 206
Ramp
Type
3-40 Ramp 1 Type3-50 Ramp 2
Type3-82 Quick Stop Ramp Type
Options
[0]
Linear
[0] Linear. Write to p.340, 350 and 382
[3] Sin3
Shape
(S3)
Par. 3-40 = [2] S-ramp Const Time
Par. 3-45 = 50%
Par. 3-46 = 50%
Par. 3-47 = 50%
Par. 3-48 = 50%
Par. 3-50 = [2] S-ramp Const Time
Par. 3-55 = 50%
Par. 3-56 = 50%
Par. 3-57 = 50%
Par. 3-58 = 50%
Par. 3-82 = [2] S-ramp Const Time
Par. 3-83 = 50%
Par. 3-84 = 50%
[4] Sin2
filter
Par. 3-40 = [2] S-ramp Const Time
Par. 3-45 = 25%
Par. 3-46 = 25%
Par. 3-47 = 25%
Par. 3-48 = 25%
Par. 3-50 = [2] S-ramp Const Time
Par. 3-55 = 25%
Par. 3-56 = 25%
Par. 3-57 = 25%
Par. 3-48 = 25%
Par. 3-82 = [2] S-ramp Const Time
Par. 3-83 = 25%
Par. 3-84 = 25%
Table 5.59 Conversion of Parameter 206
VLT 5000 series
FC 302 series
Parameter 207 Ramp up Time 1 3-41 Ramp 1 Ramp Up Time
Range
0.05 – 3600.00 s
0.01 – 3600.00 s
Table 5.60 Conversion of Parameter 207
VLT 5000 series
FC 302 series
Parameter 208 Ramp down Time 1 3-42 Ramp 1 Ramp Down
Time
Range
0.05 – 3600.00 s
0.01 – 3600.00 s
Table 5.61 Conversion of Parameter 208
VLT 5000 series
FC 302 series
Parameter 209 Ramp up Time 2 3-51 Ramp 2 Ramp Up Time
Range
0.05 – 3600.00 s
0.01 – 3600.00 s
Table 5.62 Conversion of Parameter 209
VLT 5000 series
FC 302 series
Parameter 210 Ramp down Time 2 3-52 Ramp 2 Ramp Down
Time
Range
0.05 – 3600.00 s
0.01 – 3600.00 s
Table 5.63 Conversion of Parameter 210
VLT 5000 series
FC 302 series
Parameter
211 Jog ramp time
3-80 Jog Ramp Time
Range
0.05 – 3600.00 s
0.01 – 3600.00 s
Table 5.64 Conversion of Parameter 211
VLT 5000 series
FC 302 series
Parameter 212 Quick stop ramp
time
3-81 Quick Stop Ramp
Time
Range
0.05 – 3600.00 s
0.01 – 3600.00 s
Table 5.65 Conversion of Parameter 212
VLT 5000 series
FC 302 series
Parameter
213 Jog Frequency
3-11 Jog Speed [Hz]
Range
0.0 – par. 202
0.0 – par. 4-14
Table 5.66 Conversion of Parameter 213
VLT 5000 series
FC 302 series
Parameter 214 Reference function
3-04 Reference Function
Options
[0] Sum
[0] Sum
[1] Relative
See comment below*
[2] External/Preset
[2] External/Preset
Table 5.67 Conversion of Parameter 214
*= Relative reference is added to the MRV from PROFIBUS.
VLT 5000 series
FC 302 series
Parameter
215 Preset Reference 1
3-10 Preset Reference
Range
-100.00 – 100.00%
-100.00 – 100.00%
Table 5.68 Conversion of Parameter 215
VLT 5000 series
FC 302 series
Parameter
216 Preset Reference 2
3-10 Preset Reference
Range
-100.00 – 100.00%
-100.00 – 100.00%
Table 5.69 Conversion of Parameter 216
VLT 5000 series
FC 302 series
Parameter
217 Preset Reference 3
3-10 Preset Reference
Range
-100.00 – 100.00%
-100.00 – 100.00%
Table 5.70 Conversion of Parameter 217
VLT 5000 series
FC 302 series
Parameter
218 Preset Reference 4
3-10 Preset Reference
Range
-100,00 - 100,00%
-100,00 - 100,00%
Table 5.71 Conversion of Parameter 218
VLT 5000 series
FC 302 series
Parameter 219 Catch up/slow
down value
3-12 Catch up/slow Down
Value
Range
0.00 – 100%
0.00 – 100%
Table 5.72 Conversion of Parameter 219
Parameter Mapping Lists
VLT
®
AutomationDrive FC 302 PROFIBUS Converter Operating Instructions
MG34N202 - Rev. 2013-10-15
19