4.3 Status Messages
When the drive is in status mode, status messages
automatically appear in the bottom line of the LCP display
(refer to
.) Status messages are defined in
–
.
Status
799RPM 7.83A 36.4kW
0.000
53.2%
1(1)
Auto
Hand
Off
Remote
Local
Ramping
Stop
Running
Jogging
.
.
.
Stand-by
130BB037.11
1
2
3
1
The first part of the status line indicates where the stop/
start command originates. Refer to
2
The second part of the status line indicates where the
speed control originates. Refer to
3
The last part of the status line gives the present drive
status. The status shows the operational mode that the
drive is in. Refer to
.
Illustration 4.4 Status Display
NOTICE
AUTO/REMOTE MODE
In auto/remote mode, the drive requires external
commands to execute functions.
4.4 Status Message Definitions
–
define the listed status messages.
Off
The drive does not react to any control signal
until [Auto On] or [Hand On] is pressed.
Auto
Start/stop commands are sent via the control
terminals and/or serial communication.
Hand
The navigation keys on the LCP can be used
to control the drive. Stop commands, reset,
reversing, DC brake, and other signals applied
to the control terminals can override local
control.
Table 4.10 Operating Mode
Remote
The speed reference is given from
•
External signals.
•
Serial communication.
•
Internal preset references.
Local
The drive uses reference values from the LCP.
Table 4.11 Reference Site
AC braking
AC braking was selected in
parameter 2-10 Brake Function
. The AC braking
overmagnetizes the motor to achieve a
controlled slow down.
AMA finish OK
Automatic motor adaptation (AMA) was
carried out successfully.
AMA ready
AMA is ready to start. Press [Hand On].
AMA running
AMA process is in progress.
Braking
The brake chopper is in operation. The brake
resistor absorbs the generative energy.
Braking max.
The brake chopper is in operation. The power
limit for the brake resistor defined in
parameter 2-12 Brake Power Limit (kW)
has
been reached.
Bus jog 1
PROFIdrive profile was selected in
parameter 8-10 Control Profile
. The Jog 1
function is activated via serial communication.
The motor is running with
parameter 8-90 Bus
Jog 1 Speed
.
Bus jog 2
PROFIdrive profile was selected in
parameter 8-10 Control Profile
. The Jog 2
function is activated via serial communication.
The motor is running with
parameter 8-91 Bus
Jog 2 Speed
.
Operator Interface and Driv...
VLT
®
FC Series, D1h–D8h, Da2/Db2/Da4/Db4, E1h–E4h, J8/J9
34
Danfoss A/S © 02/2019 All rights reserved.
MG94A502
4
4