10.2.15 SCR Input Busbars
To remove or reinstall the SCR busbars, use the following
steps. Refer to
Disassembly
1.
Remove the inrush card. Refer to
.
2.
Remove 3 standoffs (11 mm), 1 from each SCR
input busbar.
3.
Remove 2 screws (T25) from the black plastic
inrush support.
4.
Remove 3 screws (T30) connecting the busbars to
the SCR modules, 1 from each busbar.
5.
Remove the SCR input busbars.
NOTICE
COMPONENT ALIGNMENT
Fasten all components hand-tight, and then place the
inrush support enclosure to align components before
tightening.
Reassembly
Tighten hardware according to
1.
Position the SCR input busbars in the drive.
2.
Fasten 3 screws (T30) connecting the busbars to
the SCR modules, 1 in each busbar.
3.
Fasten 2 screws (T25) in the black plastic inrush
support.
4.
Secure 3 standoffs (11 mm), 1 in each SCR input
busbar.
5.
Replace the inrush card. Refer to
.
10.2.16 SCRs
To remove or reinstall the SCR modules, use the following
steps. Refer to
.
Disassembly
1.
Remove the SCR input busbars. Refer to
chapter 10.2.15 SCR Input Busbars
.
2.
Remove the DC(+) busbar SCR to DC coil by first
removing 1 screw (T30) that attaches the busbar
to the DC inductor.
3.
Remove 1 screw (T30) from each SCR module.
4.
Remove the insulator sheet.
5.
Remove the DC(-) busbar SCR to DC coil by first
removing 1 screw (T30).
6.
Disconnect the gate leads, 1 from each SCR
module.
7.
Remove 2 screws (T30) from each SCR module.
Reassembly
For reassembly, refer to the SCR replacement instructions
that come with the spare parts kit.