11.2.16 SCR Input Busbars
To remove or reinstall the SCR input busbars, use the
following steps. Refer to
.
Disassembly
1.
Remove the inrush card. Refer to
.
2.
Remove 2 screws (T20) from the middle of the
inrush card support bracket.
3.
Remove 2 standoffs (16 mm) from the inrush card
support bracket.
4.
Remove 3 standoffs (19 mm) connecting the
busbars to the SCR modules, 1 for each SCR input
busbar.
5.
Remove the SCR input busbars from the unit.
NOTICE
PARTS ALIGNMENT
To align all components, hand-fasten the hardware and
then position the inrush card support bracket before
tightening.
Reassembly
Tighten hardware according to
1.
Position the SCR input busbars in the unit.
2.
Fasten 3 standoffs (19 mm) connecting the
busbars to the SCR modules, 1 for each SCR input
busbar.
3.
Fasten 2 standoffs (16 mm) in the inrush card
support bracket.
4.
Secure 2 screws (T20) in the middle of the inrush
card support bracket.
5.
Replace the inrush card. Refer to
.
11.2.17 SCRs
To remove or reinstall the SCRs, use the following steps.
Refer to
Disassembly
1.
Remove the SCR input busbars. Refer to
chapter 11.2.16 SCR Input Busbars
.
2.
Remove the DC(+) busbar by removing 3 screws
(T50), 1 from each SCR module.
3.
Remove the DC(-) busbar by removing 1 screw
(T30) and 3 screws (T50), 1 from each SCR
module.
4.
Disconnect the gate leads, 1 from each SCR
module.
5.
Remove 1 screw (T30) from each of the 4 corners
of each SCR module.
Reassembly
For reassembly, use the SCR spare part instructions that
come with the parts kit. Tighten hardware according to
chapter 14.1 Fastener Torque Ratings
.