e30bf228.11
L1
L2
L3
PE
PE
u
v
w
2
1
3
5
16
17
18
14
12
8
7
10
9
4
11
13
4
6
15
90
4
1
PLC
10
Mains cable (unshielded)
2
Minimum 16 mm
2
(6 AWG) equalizing cable
11
Output contactor
3
Control cables
12
Cable insulation stripped
4
Minimum 200 mm (7.9 in) between control cables, motor
cables, and mains cables.
13
Common ground busbar. Follow local and national
requirements for cabinet grounding.
5
Mains supply
14
Brake resistor
6
Bare (unpainted) surface
15
Metal box
7
Star washers
16
Connection to motor
8
Brake cable (shielded)
17
Motor
9
Motor cable (shielded)
18
EMC cable gland
Illustration 7.5 Example of Proper EMC Installation
Drive and Motor Application...
VLT
®
FC Series, D1h–D8h, Da2/Db2/Da4/Db4, E1h–E4h, J8/J9
88
Danfoss A/S © 02/2019 All rights reserved.
MG94A502
7
7
Содержание VLT FC Series
Страница 2: ......