8.5 Dynamic Test Procedures
WARNING
RISK OF INJURY/SHOCK HAZARD
Contact with powered components can result in death or
serious injury. Before starting the drive or performing
any dynamic test procedures, take all the necessary
safety precautions for system start-up. Refer to
.
•
Do not disconnect the input cabling while
power is applied to the drive.
•
Do not touch energized parts of the drive when
connected to mains.
NOTICE
TEST ORDER
Test procedures in this section are numbered for
reference only. Perform dynamic tests in any order and
only as necessary. Always perform static tests
(
chapter 8.4 Static Test Procedures
) before applying power
to the unit.
130BF089.10
1
2
3
4
1
AC fuse
3
Brake terminals (optional)
2
Input terminals
4
Output terminals
Illustration 8.10 Power Terminals in D-sized Drive
Test Procedures
Service Guide
MG94A502