525–690 V AC
FC 102/FC 103/
FC 202
N75
N90
N110
N132
N160
N200
N250
N315
N400
FC 302
N55
N75
N90
N110
N132
N160
N200
N250
N315
Overcurrent warning
[A
rms
]
141
167
209
253
300
372
468
561
666
Overcurrent alarm
1)
(1.5 s delay)
[A
rms
]
255
255
255
255
330
483
483
585
734
Earth (ground) fault alarm
[A
rms
]
11
14
17
21
24
30
38
45
54
Short circuit alarm
[A
pk
]
459
459
459
459
593
870
869
1050
1319
Heat sink overtemperature
[
°
C]
110
110
110
110
110
110
110
110
110
Heat sink undertemperature warning
[
°
C]
0
0
0
0
0
0
0
0
0
Control card overtemperature
[
°
C]
75
75
75
75
75
75
80
80
80
Mains phase warning (30 s delay)
DC bus ripple V
pkpk
80
80
80
80
80
80
80
80
80
Mains phase alarm (60 s delay)
DC bus ripple V
pkpk
80
80
80
80
80
80
80
80
80
Table 14.7 Warning and Alarm Trip Points, D-sized Drives, 525–690 VAC
1) Based on crest factor of 1.414
380–480 V AC
FC 102/FC 103/FC 202
N355
N400
N450
N500
N560
FC 302
N315
N355
N400
N450
N500
Heat sink overtemperature trip
[
°
C (
°
F)]
110 (230)
110 (230)
110 (230)
110 (230)
100 (212)
Control card overtemperature trip
[
°
C (
°
F)]
80 (176)
80 (176)
80 (176)
80 (176)
80 (176)
Power card overtemperature trip
[
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
Fan power card overtemperature trip
[
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
Active in-rush card overtemperature trip
[
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
Table 14.8 Warning/Alarm Trip Points, E-sized Drives, 380–500 V AC
525–690 V AC
FC 102/FC 103/FC 202
N450
N500
N560
N630
N710
N800
FC 302
N355
N400
N500
N560
N630
N710
Heat sink overtemperature trip
[
°
C (
°
F)]
110 (230) 110 (230) 110 (230) 110 (230) 110 (230) 110 (230)
Control card overtemperature trip
[
°
C (
°
F)]
80 (176)
80 (176)
80 (176)
80 (176)
80 (176)
80 (176)
Power card overtemperature trip
[
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
Fan power card overtemperature trip
[
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
Active inrush card overtemperature trip
[
°
C (
°
F)]
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
85 (185)
Table 14.9 Warning and Alarm Trip Points, E-sized Drives, 525–690 V AC
Product Specifications
VLT
®
FC Series, D1h–D8h, Da2/Db2/Da4/Db4, E1h–E4h, J8/J9
322
Danfoss A/S © 02/2019 All rights reserved.
MG94A502
14
14